ML19260B215
| ML19260B215 | |
| Person / Time | |
|---|---|
| Site: | Arkansas Nuclear |
| Issue date: | 11/27/1979 |
| From: | Cavanaugh W ARKANSAS POWER & LIGHT CO. |
| To: | Reid R Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML19260B216 | List: |
| References | |
| 2-119-12, NUDOCS 7912070424 | |
| Download: ML19260B215 (2) | |
Text
,.4 ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 LITTLE ROCK, ARKANSAS 72203 (501) 371-4422 November 27, 1979 WILLIAM CAVANAUGH lli Executive Director Generation & Construction 2-119-12
- Director of Nuclear Reactor Regulation Mr. R. U. Reid, Chief Operating Reacto. Branch #4 U.S. Nuclear Regulatory Commission Washington, D. C.
20555
Subject:
Arkansas Nuclear One - Unit 2 Docket No. 50-368 License No. NPF-6 Proposed Technical Specification Change - High Pressurizer Pressure Trip Setpoint (File:
2-1511.1)
Gentlemen:
Arkansas Power & Light Company hereby requests a change to the Arkansas Nuclear One - Unit 2 (AN0-2) Technical Specifications.
A description of the proposed change and the basis is provided below.
f The High Pressurizer Pressure Trip setpoint (Table 2.2-1, item 4) is 2345 psia.
We propose to increase the trip setpoint by 23 psi to 52368 psia to eliminate a dynamic allowance imposed prior to operation.
Test data has shown an instru-ment channel response time less than assumed in the safety analysis.
Therefore, the dynamic allowance factor is no longer required.
Supplemental basis for this change has been provided in our AN0-2 Protective System Setpoint Methodology Report submitted by letter dated February 28, 1979.
Pursuant to 10CFR170.12, we have determined this change to be classified as a Class III amendment and hereby remit a check in the ancunt of $4,000.
Very truly yours, f
W f
. s-m ~<
W. Cavanaugh III/
WC:DGM:pw 1514 166 7Q}g MEMOCA N*ODLE S JUTH UTILITIES SYSTEM
~.
STATE OF ARKANSAS
)
)
SS COUNTY OF PULASKI
)
William Cavanaugh III, being duly sworn, states that he is Vice President, Generation & Construction, for Arkansas Power & Light Company; that he is authorized on the part of said Company to sign and file with
~
the Nuclear Regulatory Commission this Supplementary Information; that he has reviewed or caused to have reviewed all of the statements contained in such information, and that all such statements made and matters set forth therein are true and correct to the best of his knowledge, informa-tion and belief.
M
/
William Cave (augh Ill (J
SUBSCRIBED AND SWORN T0 before me, a Notary Public in and for the County and State abnve named, this[7 day of Nxw/JLU1979.
t f/Ab7L L/l laf
/
Notary Public /
p My Cormission Expires:
py comx.tc. rgros 9/t/01 36\\h \\61
'