Washington Public Power Supply System A JOINT OPERATING AGENCY
]
P. O. Bo x 9 6 8 3000 Gro. Wa sMi=GroN WAY FtlCML A ND, W A 9 HlN G TON 99352 PMomt (509) 375-5000 Docket t;os. 50-508 and 50-509 37 23
.c, s
itri.s Mr. R. H. Engelken, Director
,ofd y,,' J pC.,1 3 D
- 'j C !
U.S. fluclear Regulatory Commission
.a
.if
- 5/
Region V
\\'A D#
Suite 202, Walnut Creek DlaZa
'/
1990 fl. California Boulevard
,\\
W.OM'$' '
-- i Walnut Creek, CA 94596
Subject:
WPPSS f;UCLEAR PROJECTS 110S 3 & 5 IE BULLETIll NOS. 79-03 LONGITUDINAL WELD DEFECTS If1 STAltitESS STEEL PIPE SPOOLS
Reference:
Letter, D.L. Renberger to R.H. Engelken, same subject, da ted June 6,1979.
Dear Mr. Engelken:
WPPSS has recently received new information which modified its response
)
to the subject IE Bulletin submitted to you in the reference letter i
as follows:
j i
Gas strippers are used in the primary loop to remove dissolved l
gas from the primary coolant and process it to the waste gas I
Regenerative heat exchangers (one per l
management system.
stripper) for the gas strippers incorporate ASME 312-TP304L pipe manufactured by Youngstown Welding and Engineering Company as follows:
Shell - 12 inch pige, design pressure is 250 psig, design temperature is 325 F.
Channel - 12 inch pipe, design pressure is full vacuum to 80 psig design temperature is 325 F.
i
,e
-' '
- O
% s2 C, C e
7908160 O8
' / '1
.3 >
Both strippers for WNP-3 and 5 have recently been delivered to the site.
A program for the one time volumetric examination of the longitudinal welds in the above pipe is being developed to confirm that the ASME Section III acceptance criteria have not been exceeded.
A description of this and any plans for corrective action which nay be required, will be submitted as they become dVailable.
If you have any questions, please feel free to contact me.
Very truly yours, l7 l/c-Lwb Y
7 D. L. REf'BERGER Assistant Director - Technology Dil:FJ:ds cc:
D Smithpeter, BPA NRC, Office of Inspection & Enforcement, Washington D.C.
r y'n
, t, L.
vL
{Yl$