'o UNITED STATES f
~,
- 8 NUCLEAR REGULATORY COMMISSION g'
g g
- a REGION lli
%,*se'/'[g*['
h!
,g 799 ROOSEVELT ROAD GLEN ELLYN,lLLINOIS 60137
'JAN ? ? 19arl Docket No. 50-580 Docket No. 50-581 The Ohio Edisoa Company ATTN:
Mr. B. M. Miller, Manager, Generating Plant Engineering 76 South Main Street Akron, OH 44308 Gentlemen:
The enclosed Bulletin No. 80-02 is forwardea to you for action. A written response is required.
If you desire additional information re-garding this matter, please contact this office.
Sincerely,
// James G. Keppler Director
Enclosure:
IE Bulletin No. 80-02 cc w/ encl:
Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Harold W. Kohn, Ohio Power Siting Commission 1930 009 8002060 / Of 9
SSINS No.: 6820 Accession No.:
UNITED STATES 7912190653 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 1
cc i
uk January 21, 1980 W
IE Bulletin No. 80-02 INADEQUATE QUALITY ASSURANCE FOR NUCLEAR SUPPLIED EQUIPMENT Description of Circumstances:
The Marvin Engineering Company (MEC) of Inglewood, California was the subject of a special NRC inspection conducted on September 18-21, 1979 to evaluate their overall QA and QC programs which had come under severe criticism by a former Marvin Engineering employee. The special inspection was judged necessary since the Marvin Engineering Company was a known subcontractor and supplier to General Electric of BWR reactor internal feedwater spargers and feedwater thermal sleeves. The results of the NRC's inspection established that serious deficiencies exist in the implementation of the MEC quality assurance program relative to the manufacture of these components.
During this inspection, twenty seven deviations from applicable codes, and ce"1 trac-tual and regulatory requirements were documented in the areas of mateiial identification and control, process control, welding and nondestructive examination.
Correct've Action The Marvin Engineering Company has been issued the NRC's detailed inspection report of the Company, and given 30 days to inform the NRC how the deviations discussed in the report will be corrected and preventive action taken.
Action To Be Taken All BWR licensees and construction permit holders shall supply the following information within 90 days for operating plants and 120 days for plants under construction.
1.a. Have reactor feedwater spargers and thermal sleeves manufactured and/or fabricated by the Marvin Engineering Company been purchased and/or installed in your facility? Since Marvin Engineering is principally a subcontracting Company, determine if your equipment originated with the Marvin Company and was eventually supplied to your facility through another contractor / supplier.
1.b. Provide a description of this equipment to include its purchase date and its design function during both normal and accident conditions.
2.
For each piece of identified equipment, provide the perforrace history associated with its usage.
This should include the cause on any failures or malfunctions and the frequency of such events.
1930 010
IE Bulletin No. 80-02 January 21, 1980 Page 2 of 2 3.
Provide information on the suppliers and receiver's QA/QC program in d'
effect at the time of purchase.
This information should be discussed in terms of it providing sufficient bases for judging that the integrity of the equipment is sufficient to permit plant operation during normal and accident conditions.
Approved by GAO, B180225 (R0072); clearance expires 7-31-80.
Approval was given under a blanket clearance specifically for identified generic problems.
IE Bulletin No. 80-02 Enclosure January 21, 1980 RECENTLY ISSUED IE BULLETINS Bulletin Subject Date Issued Issued To No.
30-01 Ope ' 'ity of ADS Valve 1/11/80 All BWR power reactor Pneumatic Supply facilities with an OL 79-01B Environmental Qualification 1/14/80 All power reactor of Class IE Equipment facilities with an OL 79-28 Possible Malfunction of 12/7/79 All power reactor Namco Model EA 180 Limit facilities with an Switches at Elevated OL or a CP Temperatures 79-27 Loss Of Non-Class-1-E 11/30/79 All power reactor Instrumentation and facilities holding Control Power System Bus OLs and to those During Operation nearing licensing 79-26 Boron Loss From BWR 11/20/79 All BWR power reactor Control Blades facilities with an OL 79-25 Failures of Westinghouse 11/2/79 All power reactor BFD Relays In Safety-Related facilities with an Systems OL or CP 79-17 Pipe Cracks In Stagnant 10/29/79 All PWR's with an (Rev. 1)
Borated Water System At OL and for information PWR Plants to other power reactors 79-24 Frozen Lines 9/27/79 All power reactor facilities which have either OLs or cps and are in the late stage of construction 79-23 Potential Failure of 9/12/79 All Power Reactor Emergency Diesel Facilities with an Generator Field Operating License or Exciter Transformer a construction permit 79-14 Seismic Analyses For 9/7/79 All Power Reactor (Supplement 2) As-Built Safety-Related Facilities with an Piping Systems
- -DL or a CP 1930 012
~.
~