i
- p nnuou
-a
'o UNITED STATES
~,,
8 7,
NUCLEAR REGULATORY COMMISSION
'.E REGION li b[
o, 101 MARIETTA ST., N.W.. SUITE 3100 o
ATLANTA, GEORGIA 30303 JAN 171980 In Reply Refer To:
RII:JPO M 21, 50 W ;
Georgi Power Company Attn:
J. H. Miller, Jr.
Executive Vice President 270 Peachtree Street, N.W.
Atlanta, Georgia 30303 Gentlemen:
Please disregard IE Bulletin No.79-01B and enclosures dated January 14, 1980.
Enclosed is IE Bulletin No.79-01B which requires action by you with regard to your power reactor facility (ies) with an operating license.
Should you have questions regarding this Bulletin or the actions req, ired of you, please contact this office.
Sincerely, James P. O'Reilly
~71 rector
Enclosures:
1.
IE Bulletin No.79-01B with Enclosures 2.
List of Recently Issued IE Bulletins 1927 014 60020600/3'
=.)
JAN l'<
1953 Georgia Power Company g cc w/ encl:
M. Manry, Plant Manager Post Office Box 442 Baxley, Georgia 31513 C. E. Belflower Site QA Supervisor Post Office Box 442 Baxley, Georgia 31513 W. A. Widner, General Manager Nuclear Generation Georgia Power Company s
Post Office Box 4545 Atlanta, G-orgia 30303 1927 015
L UNITED STATES 3 SINS No.:
6820 NUCLEAR REGULATORY COMMISSION Accessions No.:
OFFICE OF INSPEtIION AND ENFORCEMENT 7910250528 WASHINGTON, D.C.
10555 January 14, 1980 IE Bulletin No.79-01B ENVIRONMENTAL QUALIFICATION OF CLASS IE EQUIPMENT-Description of Circumstances:
IE Bulletin No. 79-01 required the licensee to perform a detailed review of the environmental qualification of Class IE electrical equipment to ensure that the equipment will function under (i.e. during and following) postulated accident conditions.
The NRC staff has completed the initial review of licensees' responses to Bulletin No. 79-01.
Based on this review, additional information is needed to facilitate completion of the NRC evaluation of the adequacy of environmental qualification of Class IE electrical equipment in the operating facilities.
In addition to requesting more detailed information: the scope of this Bulletin is expanded to resolve safety concerns relating to design basis environments and current qualification criteria not addressed in the facilities' FSARS. These include high energy line breaks (HELB) inside and outside primary containment, aging, and submergence., " GUIDELINES FOR EVALUATING ENVIRONMENTAL QUALIFICATION OF CLASS IE ELECTRICAL EQUIPMENT IN OPERATING REACTORS", provides the guidelines and criteria the staff will use in evaluating the adequacy of the licensee's Class IE equipment evaluation in response to this Bulletin.
In general, u reporting problems encountered in the original responses and the additional information needed can be grouped into the following areas:
1.
All Class IE electrical equipment required to function under the postulated accident conditions, both inside and outside primary contain-ment, was not included in the responses.
2.
In many cases, the specific information requested by the Bulletin for each component of Class IE equipment was not reported.
3.
Different methods and/or formats were used in providing the written evidence of Class IE electrical equipment qualifications. Some licensees used the System Analysis Method which proved to be the most effective approach. This method includes the following information:
Identification of the protective plant systems required to function a.
under postulated accident conditions. The postulated accident conditions are defined as those environmental conditions resulting from both LOCA and/oc HELB inside primary containment and HELB outside the primary containment.
g{J Q}h
IE Bulletin No.79-01B Janua ry 14, 1980 Page 2 of 3 b.
Identification of the Class IE electrical equipment items within each of the systems identified in Item a, that are required to function under the postulated accident conditions.
The correlation between the environmental data requirements specified c.
in the FSAR and the environmental qualification test data for each Class IE electrical equipment item identified in Item b above.
4.
Additional data not previously addressed in IE Bulletin No. 79-01 are needed to determine the adequacy of the environmental qualification of Class IE electrical equipment. These data address component aging and operability in a submerged condition.
Actio$ To Be Taken By Licensees Of All Power Reactc* Facilities With An Operating License (Except those 11 SEP Plants Listed on Enclosure 1) 1.
Provide a " master list" of all Engineered Safety Feature Systems (Plant Pro-tection Systems) required to function under postulated accident conditions.
Accident conditions are defined as the LOCA/HELB inside containment, and HELB outside containment. For each system within (including cables, EPA's terminal blocks, etc.) the master list identify each Class IE electrical equipoent item that is required to function under accident conditions.
Pages 1 and 2 of Enclosure 2 are standard formats to be used for the " master list" with typical information included.
Electrical equipment items, which are components of systems listed in Appendix A of Enclosure 4, which are assumed to operate in the FSAR safety analysis and are relied on to mitigate design basis events are considered within the scope of this Bulletin, regardless whether or not they were classified as part of the engineered safety features when the plant was orginally licensed to operate. The necessity for further up grading of nonsafety-related plant systems will be dependent on the cutcome of the licensees and the NRC reviews subsequent to TMI/2.
2.
For each class IE electrical equipment item identified in Item 1, provide written evidence of its environmental qualification to support the capability of the item to function under postulated accident conditions.
For those class IE electrical equipment items not having adequate qualifica-tion data available, identify y, r plans for determining qualifications of these items and your schedule for completing this action. Provide this in the format of Enclosure 3.
3.
For equipment identifed in Items 1 and 2 provide service condition profiles (i.e., temperature, pressure, etc., as a function of time). These data should be provided for design basis accident conditions and qualification tests performed. This data may be provided in profile or tabular form.
1927 017
IE Bulletin No.79-01B January 14, lo80 Page 3 of 3 s
4.
Evaluate the qualification of your Class IE electrical equipment against the guidelines provided in Enclosure 4., " Interim Staff Position on Environmental Qualification of Safety-Related Electrical Equipment,"
provides supplemental information to be used with these guidelines. For the equipment identified as having " Outstanding Items" by Enclosure 3, provide a detailed " Equipment Qualification Plan." Include in this plan specific actions which will be taken to determine equipment qualification and the schedule for completing the actions.
5.
Identify the maximum expected flood level inside the primary containment resulting from pcstulated accidents.
Specify this flood level by elevation such as the 620 foot elevation.
Provide this information in the format of.
6.
Submit a " Licensee Event Report" (LER) for any Class IE electrical equipment item which has been determined as not being capable of meeting environmental qualification requirements for service intended.
Send the LER to the approp-riate NRC Regional Office within 24 hout of identification.
If plant opera-tion is to continue following identific N en, provide justification for such operation in the LER. Provide a detailed written report within 14 days of identification to the appropriate NRC Regional Office. Those items which were previously reported to the NRC as r.ot being qualified per IEB-79-01 do not require an LER.
7.
Complete the actions specified by this bulletin in accordance with the following schedule:
(a) Submit a written report required by Items 1, 2, and 3 within 45 days from receipt of this Bulletin.
(b) Submit a written report required by Items 4 and 5 within 90 days from receipt of this Bulletin.
This information is requested under the provisions of 10 CFR 50.54(f).
Accordingly, you are requested to provide within the time periods specified in Items 7.a and 7.b above, written statements of the above information, signed under oath or affirmation.
Submit the reports to the Director of the appropriate NRC Regional Office.
Send a copy of your report to the U.S. Nuclear Regulatory Commission, Office of Inspection and Enforcement, Division of Reactor Operatione Inspection, Washington, D.C.
20555.
Approved by GAO, B180225 (R0072); clearance expires 7/31/80. Approval was given under a blanket clearance specifically for identified generic problems.
Enclosures:
1.
I' SEP Plants 2.
Moster List 3.
System Compouent Evaluatien Work Sheet Instructions 018 4.
Guidelines for Evaluating Environmental Qualification of Class IE Electrical Equipment in Operating Reactors 5.
Interim Staff Position on Environmental Qualification of Safety-Related Electrical Equipment (KUREG-0588)
Note: The above enclosures are to be sent to the corporate offices only.
IE Belletin No.79-01B Enclosure Janua ry 14, 1980 RECENTLY ISSUED IE BULLETINS Besletin Subject Date Issued Issued To No.
80-01 Operability of Ads Valve 1/11/80 All BWR power reactor Pneumatic Supply facilities with an operating license 79-01B Environmental Qualifica-1/14/80 All power reactor tion c f Class IE Equipment facilities with an operating license 79-28 Possible Halfunction of 12/7/79 All power reactor Namco Model EA 180 Limit facilities with an Switches at Elevated OL or a CD Temperatures 79-27 Loss Of Non-Class-1-E 11/30/79 All power reactor Instrumentation and facilities holding Control Power System Bus OLs and to those During Operation nearing licensing 79-26 Boron Loss From BWR 11/20/79 All BWR power reactor Control Blades facilities with an OL 79-25 Failures of Westinghouse 11/2/79 All power reactor BFD Relays In Safety-Related facilities with an Systems OL or CP 79-17 Pipe Cracks In Stagnant 10/29/79 All PWR's with an (Rev. 1)
Borated Water System At OL and for information PWR Plants to other power reactors 79-24 Frozen Lines 9/27/79 All power reactor facilities which have either OLs or cps and are in the late stage of construction 79-23 Potential Failure of 9/12/79 All Power Reactor Emergency Diesel Facilities with an Generator Field Operating License or Exciter Transformer a construction permit 79-14 Seismic Analyses For 9/7/79 All Power Reactor (Supplement 2) As-Built Safety-Related Facilities with an Piping Systems OL or a CP 79-22 Possible Leakage of Tubes 9/5/79 To Each Licensee of Tritium Gas in Time-who Receives Tubes pieces for Luminosity of Tritium Gas Used in Timepieces for Luminosity 1927 019