Submits NRC Position Re Criteria for Evaluating Pipe Whip Impact & Jet Impingement Effects of Postulated Pipe Breaks. Criteria Apply to Postulated Pipe Breaks for SEP Topics III.5.A & III.5.B
ML19257C894
Person / Time
Site: La Crosse File:Dairyland Power Cooperative icon.png
Issue date: 01/04/1980
From: Ziemann D
Office of Nuclear Reactor Regulation
To: Linder F
DAIRYLAND POWER COOPERATIVE
References
TASK-03-05.A, TASK-03-05.B, TASK-3-5.A, TASK-3-5.B, TASK-RR NUDOCS 8001310055
Download: ML19257C894 (3)


Text

,

j

'i L

s.

pm REC j

J k-y[

o UNITED STATES

{ 'l ) 5- (,

p, NUCLEAR REGULATORY COMMISSION

\\g\\{

C WASHINGTON,0. C. 20555 8

] '.O

,o January 4,1980 Docket No. 50-409 Mr. Frank Linder General Manager Dairyland Power Cooperative 2615 East Avenue South La Crosse, Wisconsin 54601

Dear Mr. Linder:

RE:

SYSTEMATIC EVALUATION PROGRAM TOPICS III-5. A (EFFECTS OF PIPE BREAK ON STRUCTURE, SYSTEMS AND COMPONENTS INSIDE CONTAINMENT) AND III-5.B (PIPE BREAK OUTSIDE CONTAINMENT)

On September 12, 1979, representatives of the Systematic Evaluation Program (SEP) licensees met with the staf f and indicated their concern over uncertainty related to:

1.

The intent of footnote 14 to Regulatory Guide 1.46 and Section B.2.b.(2) of Branch Technical Position APCSB 3-1 (attached'to Standard Review Plan Section 3.6.1) with respect to when pipe whip loads are to be evaluated in impacted pipes of nominal sizes equal to or greater than that of the postulated broken pipe; and 2.

The criteria with respect to when jet impingement loads are to be evaluated in impinged pipes.

The above points are essential elements of the referenced SEP Topics.

As a result, the SEP Pranch, Division of Operating Reactors, has had frequent meetings w.ith the echanical Engineering Branch (MEB), Division of Systems Safety, to ensure that the position given below is in agreement with current criteria used in evaluating plants under review for both Construction Pemits and Operating Licenses.

It is the staff's position thr.t when evaluating the pipe whip impact and jet imoingement effects of postulated phe breaks for SEP Topics III-5.A and III-5.B, the following criteria shall apply:

1.

A whipping pipe should be considered capable of rupturing impacted pipes of smaller nominal size.

2.

A whipping pipe should be considered capable of developing through wall leakage cracks in impacted pipes of aqual or larger nominal sizes with thinner wall thicknesses.

1843 011 oOM g o o t :n p

6 s

Mr. Frank Linder January a,1080 3.

A whipping pipe may be considered incapable of rupturing or cracking impacted pipes of equal or larger nominal sizes with equal or larger wall thicknesses.

Confirmatory analysis is not required.

4.

The effects of jet impingement loads should be considered and evaluated regardless of the ratio of impinged and postulated broken pipe sizes, ever. if evaluation for pipe whip impact is not required by criterion 3 a'uove.

The staff will consiaer analytical and experimental justification for the use of less conservative criteria by the licensees on either a generic or case-by-case basis, i

,Si ncerely,

Q, 3O

.vr% n }Ww-Dennis L. Ziemann' Chief Operating Reactors Branch #2 Division of Operating Reactors i

cc: See next page 1

I i

i843 012

s Mr. Frank Linder January 4, lo8n CC Fritz Schubert,. Esquire Director, Technical Assessment Staff Attorney Division Dairyland Power Cooperative Office of Radiation Programs 2615 East Avenue South (AW-459)

La Crosse, Wisconsin 54501 U. S. Environmental Protection Agency O. S. Heistand, Jr., Esquire Crystal Mall #2 Morgan, Lewis & Bockius Arlington, Virginia 20460 1800 M Street, N. W.

Washington, D. C.

20036 U. S. Environmental Protection Agency Mr. R. E. Shimshak Federal Activities Branch La Crosse Boiling Water Reactor Region V Office Dairyland Power Cooperative ATTN:

EIS C0CRDINATOR P. O. Box 135 230 Scuth Dearborn Street Genoa, Wisccasin 54632 Chicago, Illir.ois 60t,04 Coulee Region Energy Coalition Charles Bechheefer, Esq., Chairran ATTN:

George R. Nygaard Atonic Safety and Licensing Scar:

P. O. Box 1583 U. S. "uclear Regulatory Concission La Crosse, Wisconsin 54501 Washington, D. C.

20"5 La Crosse Publ'ic Library Dr. George C. Anderson 800 Main Street Department of Oceanography La Crosse, Wisconsin 54501 University of Washington Seattle, Washington 95195 Mrs. Ellen Sabelko Society Against Nuclear Energy Mr. Ral ph S. Decker 929 Cameron Trail Route 4, Box 190D Eau C1 aire, Wisconsin 54701 Cambridge, Maryland 21613 Town Chairman K M C, Inc.

ATTN: Richard Schaffstall Town of Genoa Route 1 1747 Pennsylvania Avenue, N. W.

Genoa, Wisconsin 54632 Suite 1050 Washington, D. C. 20006 Chairman, Public Service Commission of Wisconsin DI '

jf h' y f uilp,(H Id ~gjg 4j;j jl!{

[])

Hill Farns State Office Building f([l "adison, Wisconsin 537C2 1843 013