- g "*%q'o 9'
e 8 g UNITED STATES
- )' "
E NUCLEAR REGULATORY COMMISSION e
g j
REGION I 0,
q 631 PARK AVENUE
%, +.C 9 D
,o KING OF PRUSSIA, PENNSYLVANIA 19406 JAN 141980 Docket No. 50-336 Northeast Nuclear Energy Company ATTN:
Mr. W. G. Ccunsil Vice President - Nuclear Engineering and Operations P. O. Box 270 Hartford, Connecticut 06101 Gentlemen:
Enclosed is IE Bulletin 79-018 which requires actions by you with regard to your power reactor facility with an operating license.
Should you have questions regarding this Bulletin or the actions required of you, please contact this office.
Sincerely,
/ A W.
m.
a Boyce H. Grier
~ Director
Enclosures:
1.
IE Bulletin 79-018 with Attachments 2.
List of Recently Issued IE Bulletins cc w/encls:
J. F. Opeka, Station Superintendent D. G. Diedrick, Manager of Quality Assurance J. R. Himmelwright. Licensing Sareguards Engineer iB2T050 8001 6 0
a ENCLOSURE 1 UNITED STATES SSINS No.: 6820 NUCLEAR REGULATORY COMMISSION Accessions No.:
0FFICE OF INSPECTION AND ENFORCEMENT 7910250528 WASHINGTON, D.C.
20555 IE Bulletin No.79-01B Date: January 14, 1980 Page 1 of 4 ENVIRONMENTAL QUALI7ICATION OF CLAtS IE EQUIPMENT Description of Circumstances:
IE Bulletin No. 79-01 required the licensee to perform a detailed review of the environmental qualification of Class IE electrical equipment to ensure that the equipment will function under (i.e. during and following) postulated accident conditions.
The NRC staff has completed the initial review of licensees' responses to Bulletin No. 79-01.
Based on this review, additional information is needed to facilitate completion of the NRC evaluation of the adequacy ct environmental qualification of Class IE electrical equipment in the operating facilities.
In addition to requesting more detailed information, the scope of this Bulletin is expanded to resolve safety concerns relating to design basis environments and current qualification criteria not addressed in the facilities) FSARS.
These include high energy line breaks (HELB) inside and outside primary contain-ment, aging, and submergence., " GUIDELINES FOR EVALUATING ENVIRONMENTAL QUALIFICATION OF CLASS IE ELECTRICAL EQUIPMENT IN OPERATING REACTORS", provides the guidelines and criteria the staff will use in evaluating the adequacy of the licensee's Class IE equipment evaluation in response to this Bulletin.
In general, the reporting problems encountered in the original responses and the additional information needed can be grouped into the following areas:
1.
All Class IE electrical equipment required to function under the postulated accident conditions, both inside and outside primary containment, was not included in the responses.
2.
In many cases, the specific information requested by the Bulletin for each component of Class IE equipment was not reported.
3.
Different methods and/or formats were used in providing the written evidence of Class IE electrical equipment qualifications.
Some licensees used the System Analysis Method approach.
This method includes a.
Identification of the prote under postulated accident c Entire dcmument previously conditions are defined as t entered into syscem under:
ggg{g from both LOCA and/or HELB outside t.% primary contain N o.
of Pages:
1821 M1