Forwards IE Circular 80-01, Svc Advice for GE Induction Disc Relays. No Response Required
ML19257C493
Person / Time
Site: Yankee Rowe
Issue date: 01/17/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Groce R
YANKEE ATOMIC ELECTRIC CO.
References
NUDOCS 8001290229
Download: ML19257C493 (1)


Text

Yb o

UNITED STATES 8 3p, e ( ~,,g NUCLEAR REGULATORY COMMISSION L g; aj REGION I S tg:g \\/%,...y -..,$

631 PARK AVENUE o.

9 KING OF PnUSSIA, PENNSYLVANI A 19406 Docket No. 50-29 JAN 171980 Yankee Atomic Electric Company ATTN:

Mr. Robert H. Grace Licensing Engineer 20 Turnpike Road Westborough, Massachusetts 01581 Gentlemen:

The enclosed IE Circular No. 80-01 is forwarded to you for information and, if applicable, necessary action in accordance to the attached General Electric Company Service Advice 721-152.2.. No written response to this Circular is required. If you have any questions related to the subject, please contact this office.

Sincerely, r_

MN oyce H. Grie,r f* Director

Enclosures:

1.

IE Circular No. 80-01 2.

List of Recently Issued IE Circulars CONTACT:

S. D. Ebneter (215-337-5296) cc w/encls:

H. Autio, Plant Superintendent L. E. Minnick, President 1840 097 8001290

ENCLOSURE 1 UNITED STATES SSINS No.:

6830 NUCLEAR REGULATORY COMMISSION Accessions No.:

0FFICE OF INSPECTION AND ENFORCEMENT 7912190614 WASHINGTON, D.C.

20555 IE Circular No. 80-01 Date:

January 17, 1980 Page 1 of 1 SERVICE ADVICE FOR GENERAL ELECTRIC INDUCTION DISC RELAYS Alabama Power Company reported to the NRC on October 16, 1979 a potential problem with certain General Electric Company induction disc type protective relays.

A high r than normal pick-up value was caused by petroleum jelly lubricant whici, under high temperature conditions can migrate to the backstop.

At room temperature the lubricant can become adhesive and cause pickup values to be higher than setpoint values.

General Electric (GE) laboratory confirmed some higher than normal pickup values and recommended that users determine whether relays meeting the following criteria are in use at their facilities:

(1) Relay type:

IAC, IAV, ICR, or IJCV, AND (2) The relay date code (which is printed on a 3/4" x 3/8" sticker affixed to the relay cradle) has a number less than 50, followed by any of the following two letter codes:

(a) Any first letter followed by H, J, K, L, or M; or (b) The letter combinations AN, BN, CN, DN, EN, DG, EG, FG, GG, HG, JG, KG, LG or MG.

For example, 31GK would be considered, while 50 GK or 23HN would not be considered.

Experience has shown that the cleaning procedure recommended in GJ Servico Advice 721-162.1 may not in all cases remove all of the petroleum jelly which is lodged in place.

Based on the above, licensees are advised to apply G.E. Service Advice 721-162.2 (Attachment A) to all relays that fall within the above two criteria.

No written res,7onse to this Circular is required.

If you desire acditional information regarding this matter cont Regional Office.