ENCLOSURE
[p= =%,o, UNITED STATES y
i NUCLEAR REGULATORY COMMISSION 1
3 E
WASHINGTON. O C. 20555 l
\\...'.. #'
OCT 2 41979 MEMORANDUM FOR:
E. Jordan, Assistant Director Division of Reactor Operations Inspection Office of Inspection and Enforcement FROM:
Darrell G. Eisenhut, Acting Director Division of Operating Reactors Office of Nuclear Reactor Regulation
SUBJECT:
PROPOSED IE INFORMATION NOTICE: PRESSURE SWITCH FAILURE - OHI 1 On July 14, 1979, the OHI 1 (Kansai Electric Company's 1175 MWE PWR) reactor was snutdoan due to the failure of a generating system water pressure gauge supplied by Westinghouse.
Specifically, the pressure gauge f ailed as a result of damage to the copper alloy bourdon tube, which in tarn opened a safety valve, causing a loss of pressure and subse:uent ECCS actuation.
The bourdon tube was incorrectly labeled as being.anufactured of s tainless steel.
In addition to the failed gauge, i t was foun: that other similar pressure gauges were improperly labele: at the time of their installation.
Sin:e tnis switch aas suppliec t, Westingnouse, tne concern has been raised that this same problem (improperly labeled bourdon tubes made of copoer alloy instea: of stainless steel' may exist at domestic rea: tor facilities.
As su:h, we reco rend the isssance of the propose IE In#cr atior Ncti:e (enclosed' to all PWR #acilities witn ar. Ope rating License or a Corstru c t i o n pe r--i t.
D*
?
h&}01@}k 6
f
- c. j.<- -
D1 Darrell G. Eisenhut, Acting Director os Division o' 0;erating Rea: tors O " ice of N lear Reactor Regulation En:1 os u re :
As statec
Contact:
R. Kenca'1, X2E21E CC w/ enclosure:
See next page 1707 096 80010902 N