ML19256F703
| ML19256F703 | |
| Person / Time | |
|---|---|
| Site: | Waterford |
| Issue date: | 12/07/1979 |
| From: | Seyfrit K NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV) |
| To: | Aswell D LOUISIANA POWER & LIGHT CO. |
| References | |
| NUDOCS 7912200219 | |
| Download: ML19256F703 (1) | |
Text
7ZG UNITED STATES
,0
- a,Eceq'o NUCLEAR REGULATORY COMMISSION g
- g O 's REGION IV E I8d b
611 RYAN PLAZA DHIVE,SulTE 1000
.... j ARLINGTON, TEX AS 7G012 G,#b hi, *f/'s s ...,**g December 7, 1979
,r In Reply Refer To:
RIV Docket No.
50-382/IE Bulletin No. 79-28 Louisiana Power and Light Co.
ATTN:
Mr. D. L. Aswell Vice President of Power Production 142 Delaronde Street New Orleans, Louisiana 70174 Centlemen:
Enclosed is IE Bulletin No. 79-28 which requires actioa by you with regard to your power reactor facility with an operating license or a construction permit.
Should you have questions regarding this Bulletin or the actions required of you, please contact this office.
Sincerely,'f I?
m/
,1 l
l/
<-fn,j/VLS,'hd Karl V. Seyfrit
//
Director
Enclosures:
1.
IE Bulletin No. 79-28 2.
List of Recently Issued IE Bulletins 1775 009 7 9122 00 h f O
UNITED STATES SSINS No.: 6820 NUCLEAR REGULATORY COMMISSION Accession No.:
OFFICE OF INSPECTION AND ENFORCEMENT 7910250505 WASHINGTON, D.C.
20555 IE Bulletin No. 79-28 Date: December 7, 1979 Page 1 of 2 POSSIBLE MALFUNCTION OF NAMCO MODEL EA180 LIMIT SWITCHES AT ELEVATED TEMPERATLaES Description of Circumstances:
The NRC has been recently advised through a 10 CFR 21 report from NAMCO Controls that a malfunction of a NAMCO Model EA180 stem mounted limit switch (SMLS) occurred at the Cooper Nuclear Station.
Investigation into the switch failure by the licensee revealed yellow and brown " crystal-like" resin deposits on the internal components of the switch. The affected switch is located inside the drywell containment at this facility and was being used as tSe replacement switch for an unqualified SMLS previously identified in IE B.lletin Nos.
78-04 and 79-01.
According to the manufacturer, the problem was traced to batch of top cover Baskets of which some were over-impregnated and insufficiently heat cured.
It has been determined that this condition can leave an uncured residue of " Loctite" in the gasket, which vaporizes at sustained temperatures above 175 F.
To correct the problem, the manufacturer has revised production techniques beginning September 1979 in order to better control the impregnation process and to properly heat cure the gaskets following impregnation. This problem is unique to all NAMCO Model EA180 series switches received by licensees after March 1, 1979. According to the manufacturer, the suspect switches can be identified by checking the date code which is a 4 digit number stamped on the conduit boss of the switch housing.
NMICO recommends that any EA180 series switch with a date code between 02-79 through 08-79 should have its top cover gasket replaced.
Also, licensees should request from their suppliers of equipment on which NMICO EA180 series switches are used that they check their inventory and replace top cover gaskets on switches date coded between 02-79 through 08-79.
The enclosed letter from NAMCO further describes the high-temperature environ-mental problem with the top cover gaskets used in their EA180 switches and provides recommendations to correct the problem. According to NAMCO, this letter has been sent to each customer who was shipped EA180 switches between February 21, 1979, and August 24, 1979.
Action to be Taken by Licensees of P Holders of Construction Permits:
DUPLICATE DOCUMENT 1.
Determine if your facility has switches in any safety-related Entire document previously containment, including valve po entered into system under:
containment isolation valves.
Y' 9 75 []i0 u o. of 9ases: