ML19256F687

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-28, Possible Malfunction of Namco Model EA180 Limit Switches at Elevated Temps. Action Required
ML19256F687
Person / Time
Site: Perry  
Issue date: 12/10/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Davidson D
CLEVELAND ELECTRIC ILLUMINATING CO.
References
NUDOCS 7912200103
Download: ML19256F687 (1)


Text

f/C f[,. g'o, UNITED STATES y

3,, ( (,g NUCLEAR REGULATORY COMMISSION "j/

r REGION 111 g

I 4 799 ROOSEVELT ROAD GLEN ELLYN, ILLINOIS 60137 g*k/

o Docket No. 50-440 Docket No. 50-441 DEC 101979 The Cleveland Electric Illuminating Company ATTN:

Mr. Dalwyn R. Davidson Vice President System Engineering and Construction P. O. Box 5000 Cleveland, OH 44101 Gentlemen:

Enclosed is IE Bulletin No. 79-28 which requires action by you with regard to your power reactor facilities with an operating license or a construction permit.

Should you have questions rega'rding this Bulletin or the actions required of you, please contact this office.

Sincerely, S $?

(/ James G. Kep[pfer -

Director

Enclosure:

IE Bulletin No. 79-28 cc w/ enc 1:

Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Harold W. Kohn, Power Siting Commiss; -

Mr. Daniel D. Wilt.

Attorney 1775 047 7 912200/O 3

UNITED STATES SSINS No.: 6820 NUCLEAR REGULATORY COMMISSION Accession No.:

OFFICE OF INSPECTION AND ENFORCEMENT 7910250505 WASHINGTON, D.C.

20555 December 7, 1979 IE Bulletin No. 79-28 POSSIBLE MALFUNCTION OF NAMC0 MODEL EA180 LIMIT SWITCHES AT ELEVATED TEMPERATURES Description of Circumstances:

The NRC has been recently advised through a 10 CFR 21 report from NAMCO Controls that a malfunction of a NAMCO Model EA180 stem mounted limit switch (SMLS) occurred at the Cooper Nuclear Station.

Investigation into the twiti failure by the licensee revealed yellow and brown " crystal-like" resin deposits on the internal components of the switch. The affected switch is located inside the drywell containment at this facility and was being used as the replacement switch for an unqualified SMLS previously identified in IE Bulletin Nos.

78-04 and 79-01.

According to the manufacturer,' the prcblem was traced to a batch of top cover gaskets of which some were over-impr(gnated and insufficiently heat cured.

It has been determined that this conditica can leave an uncered residue of " Loctite" in the gasket, which vaporizes at sustained temperatures above 175*F.

To correct the problem, the manufacturer has revised production techniques beginning September 1979 in order to better control the impregnation process and to properly heat cure the gaskets following impregnation.

This problem is cique to all NAMC0 Model EA180 series switches received by licensees after March 1, 1979.

According to the manufacturer, the suspect switches can be identified by checking the date code which is a 4 digit number stan; ped on the conduit boss of the switch housing.

NAMC0 recommends that any EA180 ser;es switch with a date code between 02-79 through 08-79 should have its top cover gasket replaced.

Also, licensees should request from their suppliers of equipment on which NAMC0 EA180 series switches are used that they check their inventory and replace top cover gaskets on switches date coded between 02-79 through 08-79.

The enclosed letter from NAMCO further describes the high-temperature environ-mental problem with the top cover gcskets used in their EA180 switches and provides recommendations to correct the problem.

According to NAMCO, this letter has been sent to each customer who was shipped EA180 switches between February 21, 1979, and August 24, 1979.

Action to be Taken by Licensees of Power Reactor Operating Facilities and Holders of Construction Permits:

1.

Determine if your facility has i switches in any safety-related e containment, including valve pos DUPLICATE DOCUMENT containment isolation valves.

Entire document previously entered into system under:

ANO 1775 048 s;;yes. 'W 30.