ML19256E545

From kanterella
Jump to navigation Jump to search
Ack Receipt of 790921 Final Deficiency Rept Re Defects in Ventilation Stack.Addl Info Requested
ML19256E545
Person / Time
Site: LaSalle  
Issue date: 10/24/1979
From: Fiorelli G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Reed C
COMMONWEALTH EDISON CO.
References
NUDOCS 7911080016
Download: ML19256E545 (2)


Text

4 km arco UNITED STATES NUCLEAR REGULATORY COMMISSION g

o R E GION ill 5

f 799 ROOSEVELT ROAD

/

GLEN ELLYN, ILUNOl$ 60ln Oc124 M Dpcket No. 50373 Docket No. 50374 Commonwealth Edison Company ATTN:

Mr. Cordell Reed Manager of Nuclear Operations Post Office Box 767 Chicago, IL 60690 Gentlemen:

Thank you for your final report dated September 21, 1979, pursuant to 10 CFR 50.55(<;) regarding defects in ventilation stack. Relative to your report please submit additional information addressing the following issues.

1.

'fou indicate in section V page 9 of your report that "The stack and its ring girder are presently capable of withstanding the 90 FTH design basis wind using the conditions listed above.

." Did you consider the fail-ure initiation capability represented by the " notches" associated with the known cracking and other anomalies in this analysis?

2.

What measures will be taken to preclude or mitigate the propagation of the known cracking and other anomalies during the proposed repair?

3.

Please demonstrate or indicate that th new reactor fuel presently main-tained in the fuel storage vaults would not be jeopardized if the vent stack failed and impacted on or near these or other safety related structures.

1294 047 79110800 16

3 d '

Commonwealth Edison Company.

We will complete our review of this matter upon receipt of the additional information requested.

Your cooperation with us is appreciated, s

Sincerely,

'48L Gaston Fiorelli, Chief Reactor Construction and Engineering Support Branch cc:

Mr. D. L. Peoples, Director of Nuclear Licensing Mr. L. J. Burke, Site Project Superintendent Mr. T. E. Quaka, Quality Assurance Supervisor Mr. R. H. Holyoak, Station Superintendent Central Files Reproduction Unit NRC 20b PDR Local PDR NSIC TIC Mr. Dean Hansell, Office of Assistant Attorney General i294 048