ENCLOSURE 1 NOTICE OF VIOLATIONS Metropolitan Edison Company P.O. Box 542 Reading, Pennsylvania 19603 License No. DPR-50 Based on the results of NRC inspections conducted on March 12-14, 1975 it appears that certain of your activities were not conducted in full compliance with conditions of your license as indicated below:

, A.

Contrary to 10 CFR 20.203(b) radiation areas existing in the Auxiliary Building on March 12, 1975 were not posced with the raquired signs; specifically the radiation arecs noted below:

1.-

Seal Injection Filter Area, 305' elevation-radiation levels to 15 milliroentgen per hour existed.

2.

Intermediate Cooling Water Filter Area, 205' elevation-radia-tion levels to 10 m1111 roentgen per hour existed.

3.

Concentrated Waste Pump Room, 231' elevation-radiat:.on levels to 5 milliroentgen per hour existed at the room ~ entrance.

This item is a Deficiency.

It was noted that corrective actions which included proper, posting and instructions to personnel were made prior to the conclusion of the inspection and no response to this Deficiency is required.

B.

Contrary to Technical Specification 6 2.3, written procedures were not followed as noted below:

1.

Three individuals were observed leavius the Solid Radwaste Room, a contaminated area, without monitoring themselves on March 12, 1975 as required by Health Physics Procedure 1612.

2.

Radiation Work Permits 1541, 1542, 1543 and others were not signed off by he Job Foreman as required by Health Physics Procedure 1613.

3.

A stepladder, tagged as contaminated, was stored in a cican r

area near the elevator on the 281' elevation on March 12, 1975.

Health Physics Procedure 1682 requires that contaminated equipment be stored in radiation areas or other designated areas.

This item is a Deficiency.

1452 155 5

w C7CP 7910100

~

, O N,

One Infraction and one Deficiency identified through your internal management system which were reported in a timely manner and corrected or for which corrective action was initiated are set out in the attached inspection r-port.

No additional infornation is needed for these items at this time.

O 1452 156 1

e O

=

4 9

.