PRELIMINARY NOTIFICATION June 16, 1979 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-79-160A
{
This preliminary notification constitutes EARLY notice of an event of
/
P0_SSIBLE safety or public interest significance.
The information
()
presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.
FACILITY: Carolina Powcr and Light Company-Robinson, Unit No. 2 Docket No. 50-261 Hartsville, South Carolina
SUBJECT:
INDICATION OF CRACKS IN FEEDWE.fER N0ZZLE This supplements information previously submitted in PN0 79-160.
Radiographs taken of all three steam generator main feedwater nozzles indicate interior surface cracks.
The cracks are located in the heat affect zone on the reducer side of the reducer to steam generator nozzle weld.
The replacement of the reducer section on all three steam generators will cause an extention of the refueling outage by two weeks.
Details on the crack deminsions and failure mechanism are not known at this time but are being interpreted.
Media interest is anticipated.
The licensee issued a news release on June 15.
A news release by the NRC is not planned at this time.
The State of South Carolina has been informed.
Region II (Atlanta) received notification of this additional information by tele-phone from the licensee at 11:15 a.m. on June 15.
Lontact:
G. Klingler, IE x28019; F. Nolan, IE x28019; S. Bryan, IE x28019 Distribution:
Transmitted H St 11 C Chairman Hendrie Commissioner Bradford S. J. Chilk, SECY Commissioner Kennedy Commissioner Ahearne C. C. Kammerer, CA Commissioner Gilinsky ACRS (For Distribution)
Transmitted:
MNBBJ'g)
P. Bl dg 2
- 7J_
V. Stello, IE L. V. Gossick, ED0 H. R. Denton, NRR Region D._
R ' 2 2-
~ ~ - -
H. L. Ornstein, EDO R. C. DeYoung, NRR J. J. Fouchard, PA R. J. Mattson, NRR NRR (MAIL)
R. S. Boyd,O N. M. Haller,f1PA SS Bldg D.
J. Cummings, 01A R. G. Ryan, OSP H. K. Shapar, ELD W. J. Dircks, NMSS R. iiinogue, SD S. Levine, RES PRELIMINARY NOTIFICATION 1450 201 1910 3 5 9 },
~a
.