PRELIMINARY NOTIFICATION July 3, 1979 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PN0-79-210 h

[d This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance.

The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

FACILITY:

Virginia Electric and Power Company North Anna, Unit No. 2 Docket No. 50-339 Mineral, Virginia

SUBJECT:

INDICATIONS IN FEEDWATER N0ZZLE WELDS Recent radiographs taken of the 'A' Steam Generator showed three indications in the feedwater nozzle weld areas.

Two of the indications appeared to be slag and a third appeared to be caused by porosity.

These radiographs were taken with more sensitive film and a longer exposure than the original construction radio-graphs.

A review of these results is being conducted for code acceptability as well as why they were not identified previously.

Radiographs of the other two steam generators did not identify any problems.

Media interest is not expected.

Neither the licensee nor the NRC plans a news release at this time.

The Commonwealth of Virginia has besa informed.

Region II (Atlanta) received notification of this occurrence by telephone from the resident inspector at 4:00 p.m. on July 2.

This information is current as of 8:30 a.m. on July 3.

Contact:

G. Klingler IE, x28019 F. Nolan IE, x28019 S. Bryan IE, x28019 Distribution:

Transmitted H St Chairman Hendrie Commissioner Bradford S. J. Chilk, SECY Commissioner Kennedy Commissioner Ahearne C. C. Kammerer, CA Ccmmissioner Gilinsky ACRS (For Distribution)

Transmitted:

MNBB F. Bldg 2 *.:I V. Stello. IE L. V. Gossick, E00 H. R. Denton, NRR Region U H. L. Ornstein, EC0 R. C. DeYoung, NRR J. J. Fouchard, PA R. J. Mattson, NRR N. M. Haller, MPA D. Vassallo, NRR (MAIL)

R. G. Ryan, OSP D. Eisenhut, NRR J. J. Cummings, 0IA H. K. Shapar, ELD SS Bldg R. Minogue, SD W. J. Dircks, NMSS S. Levine, RES Lang,

she ---

PRELIMINARY NOTIFICATION 1450 185 7910150

/R3