PNO-79-259:feedwater Piping Welds Inside Unit 1 Are Being Radiographed as Required by IE Bulletin 79-13.Seven Welds Have Rejectable Indications.Welds Will Be Repaired Prior to Startup
ML19256C900
Person / Time
Site: Surry  
Issue date: 07/17/1979
From: Bryan S, Mckee P, Stone J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-79-259, NUDOCS 7910150723
Download: ML19256C900 (1)


Text

..

' July 17,1979 A59 PPILIMINARY NOTIFICATION Or EVENT OR UNUSUAL OCCURRENCE--PNO-79-G6t-This oreliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest,ignificance.

The information

[.

presented is as initially received without verification or evaluation L'

and is basically all that is known by IE staff on this date.

FACILITY:

Virginia Electric and Power Company Surry, Unit Nos. 1 and 2 Docket Nos. 50-280 and 50-281 Surry, Virginia

SUBJECT:

PIJECTABLE WELDS IN FEEDWATER SYSTEM The feedwater piping welds inside Unit No. I containment are being radiographed as required by IE Bulletin 79-13 in accordance with Section III of the ASME Code.

Cracks in the steam generator nozzle area have been previously reported in PEO-79-189 and PNO-79-218.

Unit No. I radiography is 75 percent complete and seven feedwater pipe welds have rejectable indications.

Three welds have small areas of porosity; three have small areas of ince=plete fusion, and one has indications of root concavity and undercutting.

These welds were originally fabricated and exacined in accordance with USAS B31.1,1967 edition. Radiography was not required; however, by company policy feedwater line welds were radiographe d.

Cocparison of current radiographs to the original radiographs has not been ompleted at is time.

The licensee plans to repair these welds prior to startup.

Unit No. 1 is presently shut down for seismic reanalysis of safety-related piping with startup planned for August 1979. Unit No. 2 feedwater lines will be radiographed during the steam generator replacement outage which is currently in progress with startup scheduled for November 1979.

Media interest is not anticipated.

A news release is not planned by the licensee or the NRC.

The Co=monwealth of Virginia has been informed.

Region II (Atlanta) received notification of this occurrence from the licensee at 3:32 p.m. on July 16.

This information is current as of 2:00 p.m. on July 17.

Contact:

J. Stone, IE x28019; P. McKee, IE x28019; S. Bryan, IE x28019 Distribution:

Trans=itted H St Cnair=an Hendrie Com=issioner Bradford S. J. Chilk, SECY Commissioner Kennedy Commissioner Ahearne C. C. Ka= merer, CA Com=issioner Gilinsky ACRS 4' ; O (For Distribution)

Transmitted:

MNBB P. Bldg 4rafdf V. Stello, IE L. V. Gossick, EDO H. R. Denton, NRR Regica][{'__

H. L. Ornstein, EDO R. C. DeYoung, NRR J. J. Fouchard, PA R. J. Mattson, NRR N. M. Haller, MPA D. Vassallo, NRR (MAIL)

R. G. Ryan, OSP D. Eisenhut, NRR J. J. Cu=mings, OIA H. K. Shapar; ELD SS Bldg R. Minogue, SD W. J. Dircks, NMSS n7 kN PRELIMINARY NOTIFICATION b

^

ggO1

.