ML19256C650

From kanterella
Jump to navigation Jump to search
PNO-79-376:on 790828 Two Valves in One of Two Safety Injection Trains Were Found to Be Mispositioned.Caused by Operator Closing Suction Valve Instead of Sump Header Valve. Valve Error Was Immediately Corrected
ML19256C650
Person / Time
Site: Calvert Cliffs 
Issue date: 08/28/1979
From: Bryan S, Nolan F, Stone J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-79-376, NUDOCS 7910110631
Download: ML19256C650 (1)


Text

'

9 PRELIMINARY NOTIFICATION August 28, 1979 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-79-376 This preliminary notification constitutes EARLY notice of events of POSSIBLE saf ety or public interest significance.

The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

Facility:

Baltimore Gas and Electric Company Calvert Cliffs, Unit 1 Lusby, haryland '

(Docket No. 50-317)

Subject:

MISALIGNMENT OF ECCS VALVES At 6:00 a.m. on August 28, 1979 during the performance of a surveillance test, two valves in one of the two Safety Injection Trains were discovered to be misposi-tioned.

Investigation by the licensee determined that the valves were positioned on August 27, 1979 to conduct a logic surveillance test on the emergency core cooling system.

Upon completion of the emergency core cooling logic test, an operator inadvertently closed the refueling water storage tank suction valve instead of the adjacent sump header valve.

The error was discovered two shifts later at 6:00 a.m. on August 28, 1979 during the performance of a monthly talve operability test.

The valve error was immediately corrected.

The redundant containment spray and emergency core coolant systems were operable during this event.

Media interest is possible due to the public's sensitivity to nuclear power plant problems.

The State of Maryland has been informed.

A press release is not planned by the licensee or NRC.

NRC, Region I, (Philadelphia) received notification of this occurrence by tele-phone from a Regional Inspector at 3:00 p.m., August 28, 1979.

Contact:

JStone, IE x28019 FNolan, IE x28019 SBryan, IE x28019 Distribution:

Transmitted H St Chairman Hendrie Commissioner Bradford S. J. Chilk, SECY Commissioner Kennedy Commissioner Ahearne C. C. Kammerer, CA Commissioner Gilinsky ACRS (For Distribution)

Transmitted:

MNBB P. Bldg

.: c,-

V. Stello,,IE L. V. Gossick, E00 H. R. Denton, NRR

' Region '~.

H. L. Ornstein, EDO R. C. DeYoung, NRR J. J. Fouchard, PA R. J. Mattson, NRR Landow N. M. Haller, MPA D. Vassallo, NRR J. J. Cummings, DIA R. G. Ryan, OSP D. Eisenhut, NRR H. K. Shapar, ELD SS Bldg (MAIL)

W. J. Dircks', NMS$

R. Minogue, SD S. Levine, RES PRELIMINARY NOTIFICATION 7910110 6 3/

'