Forwards IE Bulletin 79-14, Seismic Analysis for As-Built Safety-Related Piping Sys. Action Required
ML19256B490
Person / Time
Site: Davis Besse 
Issue date: 07/02/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Jeffery Grant
TOLEDO EDISON CO.
References
NUDOCS 7907130291
Download: ML19256B490 (1)


Text

,pe mog#'o

' L

/

UNITED STATES l'

,,,7f' 1 NUCLEAR REGULATORY COMMISSION

[% ['*E REGION 111 799 ROOSEVELT ROAD o,

v c

GLEN E LLYN, ILLINOls 60137 JR. 7 " 79 Docket No. 50-346 Toledo Edison Company ATTN:

Mr. James S. Grant Vice President - Energy Supply Edison Plaza 300 Madison Avenue Toledo, 011 43652 Gentlemen:

The enclosed IE Bulletin No. 79-14 is forwarded to you for action.

Written responses are required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, vJamesG.[ hep >er hacb Director

Enclosure:

IE Bulletin No. 79-14 cc w/ encl:

Mr. T. Murray, Station Superintendent Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC

.) TIC liarold W. Kohn, Power Siting Commission Helen W. Evans, State of Ohio (Y

m l

7 9 0 713 003 l +

y

t U.S. NUCLEAR REGULATORY COMMISSION 6

OFFICE OF INSPECTION AND ENFORCEMENT REGIGN III July 2, 1979 IE Bulletin No. 79-14 SEISMIC ANALYSES FOR AS-BUILT SAFETY-RELnTED PIPING SYSTEMS Description of Circumstances:

Recenty two issues were identified which can cause seismic analysis of safety-related piping systems to yield nonconservative results.

One issue r.volved algebraic summation of loads in some seismic analyses. This was addressed in show cause orders for Beaver Valley, Fitzpatrick, Maine Yankee and Surry.

It was also addressed in IE Bulletin 79-07 which was sent to all power reactor licensees.

The other issue involves the accuracy of the information input for seismic analyses.

In this regard, several potentially unconservative factors were discovered and subsequently addressed in IE Bulletin 79-02 (pipe supports) and 79-04 (valve weights). During resolution of these concerns, inspection by IE end by licensees of the as-built configuration of several piping systems revealed a number of nonconformances to design documents which could potentially affect the validity of seismic analyses. Nonconformances are identified in Appendix A to this bulletin.

Because apparently significant non-conformances to design documents have occurred in a number of plants, this issue is generic.

The staff has detemined, where design specifications and drawings are used to obtain input information for seismic analysis of safety-related piping systems, that it is essential for these documents to reflect as-built con-figurations. Where subsequent use, damage or modifications affect the con-dition or configuration of safety-related piping systems as described in documents from which seismic analysis input information was obtained, the licensee must consider the need to re-evaluate the seismic analyses to con-sider the as-built configuration.