Accepts Proposal to Install 3 Alarms on the Annunciator Panel to Preclude Occurrence of non-alarmed Conditions Which Could Prevent Automatic Start of Diesel Generators
ML19256A471
Person / Time
Site: Indian Point 
Issue date: 12/21/1978
From: Schwencer A
Office of Nuclear Reactor Regulation
To: Berry G
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
References
NUDOCS 7901080245
Download: ML19256A471 (2)


Text

s

  • l!q t

y

/

b UNITED STATES y't

  • g NUCLEAR REGULATORY COMMISSION d

j WASHINGTON, D. C. 20555 j.g

[

Decemcer 21, 1978 Docket No. 50-286 Mr. George T. Berry General Manager and Chief Engineer Power Authority of the State of New York 10 Columbus Cfrcle New York, New York 10019

Dear Mr. Berry:

By letter dated March 28, 1977, we requested that Consolidated Edison review the alarm and control circuitry for the diesel generators at Indian Point Unit No. 3, and provide us with information concerning possible nonalarmed conditions which night render the diesel generators incapable of automatic start. We also requested that modifications be proposed that would correct any nonalamed disabling conditions that were identified as a result of your review. By letter dated May 19, 1977 Consolidated Edison submitted the results of their review.

In the submittal you proposed to install three alams (one for each diesel) on the annunciator panel. Each alarm would energize if the diesel stop solenoid has been activated by that diesel's lock-out relay.

In response to our letter of August 30, 1978, your letter dated September 29, 1978 indicated that (1) the annunciator will remain in alam until all the abnormal conditions have been corrected and (2) the annunciator will alam when the diesel control switch is not in the automatic position.

This is to advise you that we have reviewed your submittals and on the basis of our review conclude that the proposed modifications are acceptable and the alarm nd control circuitry for the diesel generators are adequate and should preclude occurrence of any non-alarmed conditions that could prevent automatic start of the diesel generators.

Sincerely, l@hs e

A. Schwencer, Chief Operating Reactors Branch #1 Division of Operating Reactors e

9 b

I

--Zw

~ _. _ - _

I Power Authority of the State

-2 Cecember 21, 1978 Of New York cc: White Plains Public Library Power Authority of tne State of 100 Martine Avenue New York

~

White Plains, New York 10610 Environmental Programs Mr. Lewis R. Bennett J. W. Blake, Ph.D.

Director Assistant General Manager-General Counsel 10 Columbus Circle Power Authority of the St. of NY New York, New York 10019 10 Columbus Circle Theodore A. Rebelowski New York, New York 10019 USNRC P. O. Box 38 Anthony Z. Roisman Buchanan, New York 10511 Natural Resources Deferse Council 917 - 15th Street, NW Washington, D.C.

20005 Paul S. Shemin, Esquire Assistant Attorney General State of New York Department of Law Two World Trade Center New York, New York 10047 Sarah Chasis, Esquire Natural Resource:, Defense Council 122 East 42nd Street New York, New York 10017 Mr. George M. Wilverding Licensing Supervisor Power Authority of the State of New York 10 Columbus Circle New York, New York 10019 Mr. P. W. Lyon Manager - Nuclear Operations Power Authority of the State of New York 10 Columbus Circle New York, New York 10019 Mr. J. P. Sayne, Resident Manager Indian Point 3 Nuclear Power Plant P. O. Box 215 Buchanan, New York 10511