ML19254E183

From kanterella
Jump to navigation Jump to search
Forwards Revision 2 to IE Bulletin 79-13, Cracking in Feedwater Sys Piping. Action Required
ML19254E183
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 10/19/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Reed C
COMMONWEALTH EDISON CO.
References
NUDOCS 7910310255
Download: ML19254E183 (1)


Text

lb jo, UNITED STATES

+

7, NUCLEAR REGULATORY COMMISSION

-c REGION lil 0,

[

799 ROOSEVELT ROAD U

o GLEN ELLYN. lLLINOls 6o137 OCT 191979 s

Docket No. 50-295 Qot'at No. 50-304 Commonwealth Edison Company ATTN.

Mr. Cordell Reed Manager of Nuclear Operations Post Office Box 767 Chicago, IL 60690 Gentlemen:

Enclosed is IE Bulletin No. 79-13, Revision 2 which requires action by you with regard to your pressurized water power reactor facility.

Should you have any questions regarding this Bulletin or the actions required by you, please contact this office.

Sincerely, N-s ames G. Keppler Director

Enclosures:

1.

IE Bulletin No. 79-13, Revision 2 2.

List of IE Bulletins Issued in the Last Six Months cc w/ encl:

Mr. D. L. Peoples, Director PDR of Nuclear Licensing Local PDR Mr. N. Wandke, Station NSIC Station Superintendent TIC Central Files Anthony Roisman, Esq., Attorney Director, NRR/DPM Mr. Dean Hansell, Office of Director, NRR/ DOR Assistant Attorney General 1247 353 266 7910310

~'

SSINS:

6830 Accession No.:

7908220135 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCD4ENT WASHINGTON, D.C.

20555 October 16, 1979 IE Bulletin No. 79-13 s Revision 2 CRACKING IN FEEDWATER SYSTEM PIPING Description of Circumstances:

This revision to IE Bulletin No. 79-13 is based on the results of the TJ Jio-graphic examinations and ongoing investigation of the subject problem to date since the initial Bulletin was issued. The revision reduces in scope the R2 number and extent of the piping system welds required to be examined. The requirements for reporting and action time frame remain unchanged.

On May 20, 1979, Indiana and Michigan Power i apany notified the NRC of cracking in two feedwater lines at their D. L. Cook Unit 2 facility. The cracking was discovered following a shutdown on May 19 to investigate leakage inside containment.

Leaking circumferential cracks were identified in the 16-inch feedwater elbows adjacent to two steam generator nozzle elbow welds.

Subsequent radiographic examination revealed crack indications in all eight steam generator feedwater lines at this location on both Units 1 and 2.

On May 25, 1979, a letter was sent to all PWR licensees by the Office of Nuclear Reactor Regulation which informed licensees of the D. C. Cook failurcs and requested specific information on feedwater system design, fabrication, inspection and operating histories. To further explore the generic nature of the cracking problem, the Office of Inspection and Enforcement requested licensees of PWR plants in current outages to immediately conduct volumetric examination of certain feedwater piping welds.

As a result of these actions, several other licensees with Westinghouse steam generators re.norted crack indications.

Southern California Edison reported on June 5,1979, that radiographic examination-revealed indications of cracking in feedwater nozzle-to pipe welds on two of three steam generators of San Onofre Unit 1.

On June 15, 1979, Carolina Power and Light reported that radiography showed crack indications in similar locations at their H. B.

Robinson Unit 2.

Duquesne Power and Light confirmed on June 18, 1979, that radiography has shown cracking in their Beaver Valley Unit 1 feedwater piping-to-vessel nozzle weld.

Public Service Electric and Gas Company reported on June 20, 1979 that Salem Unit 1 also has crack indications. Wisconsin Public Service company decided on June 20, 1979 to cut out a feedwater nozzle-to-pipe

~

weld which contained questionable indica' '

As of June 22, 1979 and since May 25, 15 inspected the feedwater nozzle'-to pipe t DUPLICATE DOCUMENT I

Entire document previously NOTE:

R1 and R2 indicates lines rev' entered into system under-1247 354

^"o,7,7[$$36/

No. of pages:

[

.~.-

..