ML19254A763

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-16, Vital Area Access Control. Action Required
ML19254A763
Person / Time
Site: Peach Bottom  
Issue date: 07/30/1979
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Daltroff S
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
References
NUDOCS 7908090322
Download: ML19254A763 (1)


Text

[

[o, UNITED STATES y y ) #i g

NUCLEAR REGULATORY COMMISSION 3 J '-

. [

631 PARK AVENUE C

REGION I 0,

/

,e KING OF PRUSSIA, PENNSYLVANIA 19406 Docket Nos. 50-277 JUL 301973 50-278 Philadelphia Electric Company ATTN:

Mr. S. L. Daltroff Vice President Electric Production 2301 Market Street Philadelphia, Pennsylvania 19101 Gentlemen:

Enclosed is IE Bulletin No. 79-16 which requires action by you with regard to your reactor facility (ies).

Should you have questions regarding this Bulletin or the actions required of you, please contact this office.

Sincerely, Jh/

g (VBoyce H. Grier Director

Enclosures:

1.

IE Bulletin No. 79-16 2.

List of IE Bulletins Issued in Last 12 Months cc w/encls:

W. T. Ullrich, Station Superintendent Troy B. Conner, Jr., Esquire Eugene J. Bradley, Esquire Raymond L. Hovis, Esquire Warren Rich, Esquire 7go80903 G i

ENCLOSURE 1 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Bulletin No. 79-16 Date:

July 30, 1979 Page:

1 of 4 VITAL AREA ACCESS CONTROLS Description of Circumstances:

An attempt to damage new fuel assemblies occurred recently at an operating nuclear reactor facility.

During a routine fuel inspection, the licensee discovered that a chemical liquid had been poured over 62 of 64 new fuel assemblies.

Analysis indicates that the chemical liquid was sodium hydroxide, a chemical stored and used onsite.

The licensee stores new fuel assemblies in dry storage wells on the same elevation as the spent fuel pool within the Fuel Building, a vital area.

Access t< the building is controlled by use of a coded keycard which elec-tronical,y unlocks the alarmed personnel portals.

The licensee issues coded keycards to both licensee and contractor personnel after the successful com-pletion of a background screening program.

In addition, licensee site manage-ment certifies monthly that each individual has the need for a cnded keycard in order to perform required duties.

Further access within this building is not limited by other barriers or controls.

As a result of this incident, an initial licensee audit determined that several hundred licensee and contractor personnel had access to this area during the period when the attempt to damage the fuel was made.

The audit also revealed that one coded keycard reader at a vital area portal was inaccurately recording access data at the alarm station.

Also discovered during this audit were indications of frequent " tailgating" on access through the portals. Tailgating occurs when more than one person passes through a portal on one person's authorized access.

Their passage is therefore not recorded, and unauthorized persons could gain entry in this manner.

Tailgating does not include author-ized access controlled by an escort.

Discussion of Applicable Requirements:

10 CFR 73.55(a) requires the licensees to protect against industrial sabotage committed by an insider in any position.

10 CFR 73.55(d)(7) states that access to Vital Areas shall be positively controlled and limited to individuals who are authorized access to vital equipment and who r ire such acc perform their duties.

Specific commi described in each licensee's approved DUPLICATE DOCUMENT Entire document previously entered into system under:

ANO N o.

of pc.ges: