05000267/LER-1979-059, Forwards LER 79-059/03L-0

From kanterella
(Redirected from ML19253C910)
Jump to navigation Jump to search
Forwards LER 79-059/03L-0
ML19253C910
Person / Time
Site: Fort Saint Vrain Xcel Energy icon.png
Issue date: 12/06/1979
From: Warembourg D
PUBLIC SERVICE CO. OF COLORADO
To: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML19253C911 List:
References
NUDOCS 7912120338
Download: ML19253C910 (4)


LER-1979-059, Forwards LER 79-059/03L-0
Event date:
Report date:
2671979059R00 - NRC Website

text

a.

~

l pubHe Service Company

& CdermIo 16805 Weld County Road 19.1/2, Platteville, Colorado 80651 December 6,1979 Fort St. Vrain Unit No. 1 P-79295 Mr. Karl V. Seyfrit, Directer Nuclear Regulatory Commissica Region IV Office of Inspection and Enforcement 611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76012 REF: Facility Operating License No. DPR-34 Docket No. 50-267 D2ar Mr. Seyfrit:

EncJesed please find a copy of Reportable Occurrence Report No. 50-267/

79-59, Final, submitted per the requirements of Technical Specification AC 7. 5. 2 (. ) 2.

b Also, please find enclosed cre copy of the Licensee Event Report for Reportable Occurrence Report No. 50-267/79-59.

Very truly yours, on Warembourg Manager, Nuclear Production DR/cis cc:

Director, MIPC OD1 1542 152 s

lll 7 912120 33 F

e REPORT DATE:

December 6, 19 79 _____

REPORTABLE OCCURRENCE 79-59 ISSUE O OCCURRENCE DATE:

November 9,1979 Page 1 of 3 FORT ST. VRAIN NUCLEAR GENERATING STATION PUBLIC SERVICE CCFP/NY OF COLORADO 16805 WELD COUNTY ROAD 191/2 PLATTEVILLE, COLORADO 80651 REPORT No. 50-267/79-59/03-L-0 Final IDENTIFICATION OF OCCURRENCE:

On November 9,1979, with the reactor in a shutdown condition, engineering per-sonnel observed that boiler feed snubber BFS-412 was inoperable.

Since the reactor had been operated at power during the st rveillance interval, this constitutes operation in a degraded mode of LCO 4.3.10, and is reportable per Fort St. Vrain Technical Specification AC 7.5.2(b) 2.

EVENT

DESCRIPTION

On November 9,1979, with the reactor shutdown for scheduled maintenance, engineering personnel observed that the oil reservoir for boiler feed snubber BFS-412 was empty. See details of Figure 1.

Because the oil reservoir was empty, this snubber was determined to be inoperable.

This snubber had been verified operable during performance of the previous sur-veillance.

CAUSE

DESCRIPTION:

Reason for snubber being inoperable was an empty hydraulic oil reservoir.

CORRECTIVE ACTION:

The snubber hydraulic oil reservoir was refilled and the snubber returned to s ervice. The present surveillance interval is 124 days + 25%. No change is required as a result of this occurrence.

No further corrective action is anticipated or required.

1542 153

REPORTABLE OCCURRENCE 79.4 ISSUE 0 Page 2 of 3 figs. 200, 201 011 Reservoir 'Jas Empty

.NUSSER VALVE VENT-SHIPPING PLUG TU8tNG SEAL NUT

.E5 y

7, p a ~=>=~

.E E..

fr;e "j'4Er/ / h.

W

~

Ydristou co 4'.

/

= ~Ur -

e= ~ur =-

/:Pa /

_,,,c _.

~,,E cuo,

~,4 1::nw,

,,ca,c h.-

y cm,,,../

MSULATIC 1542 154 FIGURE 1 O

a

REPORTABLE OCCURRENCE 79-59 ISSUE O Page 3 of 3

, 'i A

G/'-

1 Prepared by:

Cd.

L, M pc/(_

~~

Cathy C. Hirsch Technical Services Technician

/

r

/'

AD Reviewed by: v'/'/-7/.' e J. W. Cahm Technical Services Supervisor Reviewed by:

b

~~~

Frank M. Mathie Operations Manager Approved by:

d

' g e o,,,, Q Don Warembourg

[/

Manager, Nuclear Producfion 1542 155