VistnixrA Er.ncriexc ann Pownic Co3tmxy Rrcatnown,Vinoux zA conut October 26, 1979
'f9 - J h Q - 0 0 0 Mr. James P. O'Reilly, Director Serial No. 881 Office of Inspection and Enforcement P0/FHT:scj U. S. Nuclear Regulatory Commission Docket No. 50-338 Region II License No. NPF-4 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303
Dear Mr. O'Reilly:
Under the provisions of 10CFR21, NRC Region II was notified on October 23, 1979, that a potential significant deficiency or substantial safety hazard existed at North Anna Power Station, Unit 1.
In accordance with the reporting requirements of the above regulations, the following information is submitted:
A.
Name and address of reporting individual:
C. M. Stallings Virginia Electric and Power Company P. O. Box 26666 Richmond, Virginia 23261 B.
Facility, activity and/or component affected:
Control cable being in-stalled on a design change for degraded grid voltage, North Anna Power Station Unit No. 1.
C.
Mame of firm supplying the component, activity or service:
Cerro/Rockbestos Corporation, Nicoll & Canner Street, New Haven, Connecticut 06504.
D.
Description of defect, deficiency, or failure to comply:
A partially ex-posed wire was discovered in the area of an insulation splice, in a con-trol cable bundle (IENSU0C077) of twelve wires of size #14 AWG (NJK45-14).
E.
Date of determination of reportability:
10/22/79.
F.
Similar components, activities, or services: no safety-related systems.
G.
Corrective action which has been, is being, or will be taken, the individu-al responsible and the length of time to complete the action: The faulty splice was removed and the cable was properly terminated.
H.
Other information:
All like cabic (spools 3187-150, 3187-151 and 3187-153) has been returned to the manufacturer for examination to determine if this is a generic problem.
1537 106 voici soc ra
Vinoixta ELECTalC AND Powra COMPANY TO Mr. James P. O'Reilly 2
Any additional information regarding the above topic will be submitted as a follow-up report.
Should you require further information, please contact this office.
Very truly yours,
- h. k ht?dAs<