e arc,

o

[

'o UNITED STATES 8'

NUCLEAR REGULATORY COMMISSION s

n

'U J.

E REGION 111 o,

[

799 ROOSEVELT ROAD

%..v '

e GLEN E LLYN, lLLINOIS 60137

.+

Docket No. 50-461 Docket No. 50-462 Illinois Power Company ATTN:

Mr. W. C. Gerstner Executive Vice President 500 South 27th Street Decatur, IL 62525 Gentlemen:

The enclosed IE Circular No. 79-23 is forwarded to you for your infor-mation. No written response to this circular is required.

If you have any questions related to the subject, please contact this office.

Sincerely, JamesG.Keppfe.tbw

.nuh/&

r Director

Enclosure:

IE Circular No. 79-23 cc w/ encl:

Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Mr. Dean Hansell, Office of Assistant Attorney General 1540 156 7912110 262 h

SSINS No.:

6830 Accession No.-

7910250496 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 November 26, 1979 IE Circular No. 79-23 MOTOR STARTERS AND CONTACTORS FAILED TO OPERATE Gould, Inc., Electrical Products Group, reported to the NRC on September 11, 1979 potential defects in certain NEMA size 3, Starters and Contactors.

A possible binding or seisure of the carrier assembly, within the support plate of the stationary contact assembly, is caused by an undersized dimension of the support legs.

Starters and contactors with date code 7822 to 7935, model and serial numbers A10, All, A12, A13, A14, A20, A21, A22, and P10 are involved.

Faulty units were manufactured and distributed between June 1, 1978 and August 30, 1979.

The attached listing of nuclear plants, which have received some of this motor control equipment, represents a preliminary check of shipment records.

This listing, however, may not be complete.

Gould, Inc., will recall uninstalled items for retrofit and has retrofit kits available for field installation.

Based on the above, licensees are advised to verify all motor starter and contactor shipments received from Gould, Inc., between June 1, 1978 and August 30, 1979, and assure that applicable model and serial number components are corrected by retrofit and subsequent electrical operation tests.

No written response to this Circular is required.

If you desire additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.

Enclosures:

1.

List of Plants That May Have Received Defective

]}4Q

]}/

Starter or Contactors 2.

List of Currently Issued IE Circulars DUPLICATE DOCUMENT Entire document previously entered into system under:

h h

ANO No. of pages:

___ __.