3 u

DISTRIBUTION:

Docket File NRC PDR L PDR ORB #4 Rdg VStello BGrimes C ter Docket No. 50-289

.: sy78,,,

GZwetzig RIngram Attorney, OELD OI&E (3)

Mr. J. G. Herbein Vice President TERA, DSB Metropolitan Edison Company

. JRBuchanan P. O. Box 542 Gray F'Ie Read'ng, Pennsylvania 19603

Dear Mr. Herbein:

In order that we say continue our review for Three Mile Island !!uclear Station, Unit No.1 (TMI-1) of.the consequences of crane failures when handling heavy loads, we find we need additional information.

The speci#de infonnation needed is.given in the enclosure.

It is requested that you provide this jnfonnation within 45 days of receipt of this letter. It is. also. requested that you suWt by the same date an amendment to your. Technical Specification Change Request No. 38, dated September 21,1976, if.your responses to this request for additional information and the responses contained in your letter of January 31,1978, indicate that.such changes are needed.

Sincerely, i.vndW8d' Robert W. Reid, Chief Operating Reactors Branch f4 Division of Operating Reactors

Enclosure:

~

Request for Additional Information 150a 181 cc w/enclosum:

See next page

@Y f.

OR874:00R g 4:p0R l

GZwetzig:rf TReid

.r t

10//(g/78 10//f/78

~t NRC PORM 318 (9 76) NRCM 0240

. W u. s.eevamousur mmvises orrican se7e-sam 7910810

s fletropoli tan Ecison Coi..pany cc:

G. F. Trowbriage, Esqui re Shaw, Pi ttnan, Potts & Trowbric;.

180011 Street, N.W.

Washi ngton, D.C.

20036 GPU Service Corporation Richard W. Heward, Pro,iect ;1anager fir. T. Gary Broughton, Safety and Licensing ffanager 260 Cherry Hill Road Parsippany, flew Jersey 07054 Pennsylvania Electric Company fir. R. W. Conrad Vice President, Generation 1001 Croad Street Johnstown, Pennsylvania 15907

'tiss liary V. Southard, Chairman Citizens for a Safe Environment P. O. Box 405 Harrisburg, Pennsylvania 17108 Government Publications Section State Library of Pennsylvania Box 1601 (Eaucation Builuing)

Harrisburg, Pennsylvania 17126 g

REQUEST FOR ADDITIONAL INFORMATION CONSEQUENCES OF CRANE FAILURES THREE MILE ISLAND NUCLEAR STATION, UNIT N0. 1 DOCKET NO. 50-312 1.

In your letters of February 14, 1976 and January 31, 1978, you define a transfer oath for moving a fuel cask from the transporter to eleva-tion 348'-0".

In your letter of January 31, 1978 you also define a

" Unit 1 main hook travel area for icsds over 15 tons." Among other uses, this travel area could be used for transporting a shipping cask to the Receiving / Shipping Area.

Inasmuch as the cask transfer path was selected to assure the safety of that specific movement, provide the basis for the acceptability of moving casks or other loads weighing from 15 to 110 tons anywhere within the " Unit 1 main hook travel area for loads over 15 tons."

2.

Inasmuch as no restrictions are placed on the limits of travel for loads weighing between 3000 pounds and 15 tons (except in the vicinity of the spent fuel pools), either:

(1) provide an analysis demonstrat-ing that dropping a 15 ton load at any point in the permissible area of travel (outside the " Unit 1 main hook travel area for loads over 15 tons") from the maximum permissible height would not damage redundant channels of safety related equipment or electrical cables, or (2) define a restricted area of travel and a restricted lift height and provide a similar analysis for these more restrictive conditions.

\\SDS \\85