Forwards IE Circular 79-17, Contact Problem in SB-12 Switches on GE Metalclad Circuit Breakers. No Action Required
ML19249B683
Person / Time
Site: Waterford 
Issue date: 08/14/1979
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Aswell D
LOUISIANA POWER & LIGHT CO.
References
NUDOCS 7909040666
Download: ML19249B683 (1)


Text

7 b

gn necq UNITED STATES

+

5 'i{W,h;,> '

. c 'l NUCLEAR Rr'ULATORY COMMISSION o

tlEGION IV

%'o,, b2

. '/

G11 HYAN PL AZA DRIVE, SulTE 1000 0,

g AR LINGToN, T E X AS 7G012

-E 4

August 14, 1979 la Reply Refer Ic:

RIV Docket No.

50-282/IE Circular ';o. 79-17 Louisiana Power and Light Co.

ATTN:

Mr. D. L. Aswell

" ice President of Power Production 142 Delaronce Screet New Orleans, Louisiana 70174 Gentlemen:

This IE Circular is provided as an early notification of a possible significant matter.

It is expected that recipients will review the inforraation for possible applicability to their facilities.

No specific action or response is requested at this tine.

If further NRC evaluations so indicate, an IE Bulletin will be issued to recocaend or request specific licensee actions.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

Sincerely, M

1

  1. m" L. &

./

Karl V.

Seyfrit Director

Enclosures:

1.

IE Circular No. 79-17 2.

List of IE Circulars Issued in the Last 6 Months o ; ~ s r,a a) U

  • 1L O..

7909 04 0 b[p h

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT b'ASIIINGTON, D.C.

20555 IE Circular No. 79-17 Date: August 14, 1979 Page 1 of 1 CO.OJT =EC M IN 53-12 SWITCHES ON GENERAL ELECTRIC METALCLAD CIRCUIT BRET ::

The C -

_ Electric Ca pacy, Switchgear Department in Philadelphia, reported to the ZZ~ :: July 3, 1979,, an intermittent contact problem in SB-12 switches.

This in =- "ttent contact problem will cause a lack of continuity through the "a" cent::: of the switch that is used to energize the trip coil of the circuit breaker.

- vestigation disc.losed that a die used to form a hole in the contact a rms o # --- switch had worn, resulting in elongated holes.

This condition could permit the contact bridge member to move laterally relative to the contact arm, occasionally resulting in improper "a" contact wipe. The worn die has been corrected, and all switches shipped on or af ter July 1, 1979, include this correction.

A review of the history of these components indicates that switches shipped in the time period of August 1, 1978 to July 1, 1979, could have this problea.

The trip coil and auxiliary switch portion of the trip circuit is monitored for continuity by a red light on the front door of the switchgear.

This light is lit when the breaker is closed and the control circuits are energized.

If the rdd light is lit, this indicates that the "a" contacts of the switch are closed, and that a trip signal will trip the breaker.

Based on the above, the licensees are advised to do the following:

1.

Insure that all General Electric Company Metalclad Circuit Breakers shipped to your facilities during the period from August 1, 1978 to July 1, 1979 and used in or affecting the operation of safety related equipment are furnished with new SB-12 control switches as promptly as possible.

2.

Pending replacement of SB-12 control switches, administrative controls should be initiated to assure the red light which demonstrates contact continuity, is lit and remains lit each time these circuit breakers are closed.

No written response to this circular is required.

If you require additional inforaation regarding this subject, contact the Director of the appropriate NRC Regional Office.

D D

uv c, a

Ju M L L a 9

g]d 7/s20 a

m,-..

w.m

IE Circular No. 79-17 August 14, 1979 LISTING OF IE CIRCULARS ISSUED IN LAST SIX MONTHS Circ __ar Subj ect Date of Issued To No.

Issue 79-03 Inadequate Guard 2/23/79 All Holders of and Training - Qualifica-applicants for Special tion and Falsified Nuclear Material Licenses Training Records in Safeguards Group I 79-04 Loose Locking Nut 3/16/79 All Holders of Reactor On Limitorque Valve Operating License (OL) or Operators Construction Permits (CP) 79-05 Moisture Leakage in 3/20/79 All Holders of Reactor Stranded Wire Conductors Operating License (0L) or Construction Permits (CP) 79-06 Failure to Use Syringe 4/19/79 All Holders of Medical and Battle Shields in Licensees except Teletherapy Nuclea r Medicine Licensees 79-07 Unexpected Speed Increase 5/2/79 All Holders of BWR Operating of Reactor Recirculation Licenses (OLs) or Construc-MG Set Resulted in Reactor tion Permits (cps)

Power Increase 79-08 Attempted Extortion - Low 5/18/79 All Fuel Facilities and Enriched Uranium Reactors Licensed by NRC 79-09 Occurrences of Split or 6/22/79 All Materials Priority I, Punctured Regulator Fuel Cycle and Operating Diaphragas in Certain Reactor Licenses (OL)

Self Contained breathing Apparatus 75-10 Pipefittings Manufactured 6/26/79 All Power Reactor Licensees frca Unacceptable Material with a Construction Permit.

and/or Operating License (OL) 79-11 Design / Construction 6/27/79 All Holders of and Applicants Interface Problem for Power Reactor Cons truction Permits (CP)

Enclosure Page 1 of 2 sy\\ q s r r.

u %2

  • n s s ;p

IE Circular No. 79-17 August 14, 1979 79-12 Potential Diesel Generator 6/28/79 All Power Reactor Licensee with Turbocharger Problem a Construction Permit (CP) and/or Operating License (OL) 79-1:

7.eplacecent f Diesel 7/13/79 All Power Reactor Licensee Fire Purp Starting with a Construction Permit Contact;:s (CP) and/or Operating Licensee (OL) 79-14 Unauthorined Procurement 7/13/79 All Medical Licensees and Distribution of Except Teletheraphy XE-133 Medical Licensees and to all Radiopharmaceutical Suppliers 79-15 Bursting of High Pressure 8/8/79 All Materials Priority I, Hose and Malfunction of Fuel Cycle and Operating Relief Valve "0" Ring in Power Reactor Licensees Certain Self-contained Breathing Apparatus 79-16 Excessive-Radiation 8/16/79 All Radiography Exposures to Members Licensees of the General Public and a Radiographer Enclosure I ) 'f 0

Page 2 of 2 D

.J s Jt o rp j g 7, r a bib J

_ b _rd _a m,

  • M' < ' 's:.i ti c.,,.,