ML19247B823

From kanterella
Jump to navigation Jump to search
Requests Util Submit Proposed Secondary Water Chemistry Program to Be Incorporated in New License Condition. Current STS for All PWRs Are Ineffective Re Steam Generator Tube Degradation.Model License Condition Encl
ML19247B823
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 08/01/1979
From: Schwencer A
Office of Nuclear Reactor Regulation
To: Reed C
COMMONWEALTH EDISON CO.
References
NUDOCS 7908130569
Download: ML19247B823 (4)


Text

TOb

[paarcq#'o M

UNITED STATES f

f y,,G j NUCLEAR REGULATORY COMMISSION

,8

- M g

WASHIP.GTON, D. C. 20555

/

/23UST 1

M9 Docket Nos. 50-295 and 50-304

19. Cordell Reed Assistant Vice President Commonwealth Edison Company Post Office Box 767 Chicago, Illinois 60690

Dear Mr. Reed:

In August 1976 we sent letters to the majority of licensees who operate Pressurized Water Reactors (PWRs) regarding the control of secondary water chemistry to inhibit corrosion of steam generator tubes.

The letters requested the licensees to propose Technical Specification changes to incorporate limiting conditions for operation and surveillance requirements for secondary water chemistry parameters.

Model Technical Specifications, which reflected the requirements contained in the Commission's Standard Technical Specifications (STS), were included for guidance.

Many licensees objected to the Model Technical Specifications principally on the basis that they could unnecessarily restrict plant operation.

The majority of these licensees submitted alternative approaches that were directed more toward monitoring and record keeping rather than specific limits on chemistry parameters.

At the time of our request, we recognized that a major disadvantage of the Technical Specifications was a potential decrease in operational flexibility, but our request was motivated by an overriding concern for steam generator tube integrity.

Our objective was to provide added assurance that licensees would properly monitor and control secondary water chemistry to limit corrosion of steam generator tubes.

However, based on the experience and knowledge gained since 1976, we have now concluded that Technical Specification limits would not be the most effective way of accomplishing this objective.

Due to the complexity of the corrosion phenomena involved, and the state-of-the-art as it exists today, we believe that a more effective approach would be to institute a license condition that requires the implementation of a secondary water chemistry monitoring and control program containing appropriate procedures and administrative controls. A Model License Condition that is acceptable to the staff for this purpose is enclosed, c181N f

70081303 (O

Mr. Cordell Reed tmusT 1

1979 The required program and procedures would be developed by the licensees, with any needed input from their reactor vendors or other consultants, cnd thus could more readily account for site and plant specific factors that affect chemistry conditions in the steam generators.

In our view, such a li:ense condition would provide assurance that licensees would devote proper attention to controlling secondary water chemistry, while also providing the needed flexibility to allow them to more effectively deal with any off-normal conditions that might arise.

Moreover, we have concluded that such a license condition, in conjunction with existing Technical Specifications on ste.am generator tube leakage and inservice inspection, would provide the most practical and comprehensive means of assuring that steam gnerator tube integrity is maintained.

Consequently, we request that you submit a proposed amendment to your license to incorporate the requirements of the enclosed Model License Condition into the body of your license within 60 days, If you previously submitted an application for a license amendment concerning steam generator monitoring requirements prior to March 22, 1978, you need not remit a fee for the license amendment requested by this letter.

If you have not submitted a license amendment request prior to March 22, 1978, you should remit a Class III fee with your application for Zion 1 and a Class I fee for Zion 2.

I f you have any questions, please contact us.

No further action will be taken on any proposed Technical Specification changes you may have submitted in response to our August 1976 request.

Such change requests will be considered withdrawn unless you express objections within 60 days.

Sincerely, ufbli 6

7 A. Schwencer, Chief Operating Reactors Branch #1 Division of Operating Reactors

Enclosure:

Model License Condition cc: w/ enclosure:

See next page p e pa ? -

%dOU

ENCLOSURE MODEL LICENSE CONDITION SECONDARY 'iATER CHEMISTRY b'ONITORING The licensee shall implement a secondary water chemistry r.onitoring progran to inhibit steam generator tube degradation. This orogram shall include:

1.

Identificatien of a sarpling schedule for the critical parameters and control points for these parameters; 2.

Identificatien of the crocedures used to quantify ;arameters that are critical to centrol coints; 3.

Identificaticn of prccess sampling points; 4.

Precedure fcr the recording and manace.ent of data; 5.

Procedures defining corrective actions for off control point chemistry conditions; and 6.

A procedure identifying the authority resocnsible for the inter-pretation of the data, and the secuence and timing of administrative events required to initiate corrective action, b1ddIv'h'