Text
tkA R f C(;
.p UNITED STATES
,{
,0, y
') 2. g
,g NUCLEAR REGULATORY COMMISSION
- t
- f %d}l(. t REGtON V
~
% '( hh
,[
1990 N. CALIFORNI A BOULEVARD
,d" SUITE 202, WALNUT CREEK PLAZA WALNUT CREEK, CAllFORNI A 9 A596 July 26,1979 Docket No. 50-312 Sacramento Municipal Utility District P. O. Box 15830 Sacramento, California 95813 Attention: Mr. John J. Mattimoe Assistant General Manager Gentlemen:
Enclosed is IE Bulletin No. 79-16 which requires action by you with regard to your reactor facility (ies).
Should you have questions regarding this Bulletin or the act%ns re-quired of you, please contact this office.
Sincerely, ffWm4GL R. H. Engelken Diree. tor
Enclosures:
1.
IE Bulletin No. 79-16 2.
List of IE Bulletins Issued in Last 12 Months cc w/ enclosures:
R. J. Rodriguez, SMUD L. G. Schwieger, SMUD 42i 175 7908060 7 7 rV 0-
UflITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ErlFORCEMEi4T WASHINGTON, D.C.
20555 July 26,1979 IE Bulletin No. 79-16 VITAL AREA ACCESS CONTROLS Description of Circumstances:
An attempt to damage new fuel assemblies occurred recently at an operating nuclear reactor facility. During a routine fuel inspection, the licensee discovered that a chemical liquid had been poured over 62 of 64 new fuel assemblies. Analysis indicated that the chemical liquid was sodium hydroxide, a chemical stored and used onsite.
The licensee stores new fuel assemblies in dry storage wells on the same elevation as the spent fuel pool within the Fuel Building, a vital area.
Access to the building is controlled by use of a coded keycard which elec-tronically unlocks the alarmed personnel portals.
The licensee issues coded keycards to both licensee and contractor personnel af ter the successful com-pletion of a background screening program.
In addition, licensee site manage-ment certifies monthly that each individual has the need for a coded keycard in order to perform required duties. Further access within this building is not limited by other barriers or controls.
As a result of this incident, an initial licensee audit determined that several hundred licensee and contractor personnel had access to this area during the period when the attempt to damage the fuel was made.
The audit also revealed that one coded keycard reader at a vital area portal was inaccurately recording access data at the alarm station. Also discovered during this audit were indications of frequent " tailgating" on access tt. rough the portals. Tailgating occurs when more than one person passes through a portal on one person's authorized access. Their passage is therefore not recorded, and unauthorized persons could gain entry in this manner.
Tailgating does not include author-ized access controlled by an escort.
Discussion of Applicable Requirements:
10 CFR 73.55(a) requires the liccasees to protect against industrial sabotage ccmitted by an insider in any position.
10 CFR 73.55(d)(7) states that access to vital areas shall be positively controlled and limited to individuals who are authorized access to vital equipment and who require such access to perform their duties. Specific cctmitments implementing this regulation are described in each licensee's approved Security PP-IDUPLICATE DOCUMENT
- i; Entire document previously entered u Jinto system under:
421 176 f
asO 9 90BOEl76 i
1 No. of pages:
b 31*
-