ML19247A968

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-16, Vital Area Access Control. Action Required
ML19247A968
Person / Time
Site: Trojan File:Portland General Electric icon.png
Issue date: 07/26/1979
From: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To: Goodwin C
PORTLAND GENERAL ELECTRIC CO.
References
NUDOCS 7908060058
Download: ML19247A968 (1)


Text

A p '* " %g s

o UNITED sT ATES

l., _

8 \\j'j,,, c I,h NUCLEAR REGULATORY COMMISSION

/^'

s ? T*

.2 HEGION V S 2 ><

[Y 1990 N. CAllFORNIA BOULEVARD

% ' \\/ " o SUITE 202, WALNUT CREEK PLAZA

  • e,,*

WALNUT CR EE K, CALIFORNI A 94596 July 26,19'/9 Docket No. 50-344 Portland General Electric Company 121 S. W. Salmon Street Portland, Oregon 97204 Attention: Mr. Charles Goodwin Assistant Vice President Gentlemen:

Enclosed is IE Bulletin No. 79-16 which requires action by you with regard to your reactor facility (ies).

Should you have questions regarding this Bulletin or the actions re-quired of you, please contact this office.

Sincerely,

$Y,~fS0 R. H. Engelken Director

Enclosures:

1.

IE Bulletin No. 79-16 2.

List of IE Bulletins Issued in Last 12 Months cc w/ enclosures:

B. Withers, PGE F. Gaidos, PGE 421 202 est 7

7008080

'^

i UtlITED STATES tlUCLEAR REGULATORY COMMISSI0t1 0FFICE OF IflSPECTI0tt AtID EtiFORCEMEitT WASHIi4GT0ti, D.C.

20555 July 26,1979 IE Bulletin flo. 79-16 VITAL AREA ACCESS C0tlTROLS Description of Circumstances:

An attempt to damage new fuel assemblies occurred recently at an operating nuclear reactor facility. During a routine fuel inspection, the licensee discovered that a chemical liquid had been poured over 62 of 64 new fuel assemblies. Analysis indicated that the chemical liquid was sodium hydroxide, a chemical stored and used onsite.

The licensee stores new fuel assemblies in dry storage wells on the same elevation as the spent fuel pool within the Fuel Building, a vital area.

Access to the building is contrciled by use of a ceded keycard which elec-tronically unlocks the alarmed per:onnel portals. The licensee issues coded keycards to both licensee and contractor personnel af ter the successful com-pletion of a background screening program.

In addition, licensee site manage-ment certifies monthly that each individual has the need for a coded keycard in order to perform required duties.

Further access within this building is not limited by other barriers or controls.

As a result of this incident, an initial licensee audit determined that several hundred licensee and contractor personnel had access to this area during the period when the attempt to damage the fuel was made.

The audit also revealed that one coded keycard reader at a vital area portal was inaccurately recording access data at the alarm station. Also discovered during this audit were indications of frequent " tailgating" on access through the portals. Tailgating occurs when more than one person passes through a portal on one person's authorized access. Their passage is therefore not recorded, and unauthorized persons could gain entry in this manner. Tailgating does not include author-ized access controlled by an escort.

Discussion of Applicable Requirements:

10 CFR 73.55(a) requires the licensees to protect against industrial sabotage committed by an insider in any position.

10 CFR 73.55(d)(7) states that access to vital areas shall be positively controlled and limited to individuals who are authorized access to vital equipment and who require such access to perform their duties. Specific commitments implementing this regulation are described

~~

in each licensee's approved Security - T

~

~~4 DUPLICATE DOCUMENT Entire document previously entered into system under:

b[(Mh/ 7b ANO b

No. of pages:

e c

--