Ack Receipt of 790430 Submission of Revision 2 to Fire Protection Plan.Forwards Discussion of Two Points Found Unacceptable.Plan Should Apply to Both Unit 1 & Unit 2
ML19247A327
Person / Time
Site: Arkansas Nuclear  
Issue date: 06/13/1979
From: Reid R, Stolz J
Office of Nuclear Reactor Regulation
To: Cavanaugh W
ARKANSAS POWER & LIGHT CO.
References
NUDOCS 7907300560
Download: ML19247A327 (3)


Text

o.

f l D)('tjQ$ p'

.r-a** a'c ff w)%,

UNITED STATES

,rr g

NUCLEAR REGULATORY COMMISSION f

WASHINGTON, D. C. 20555

%]}

~

/

y

...../

June 13, 1979 Docket tio.-

50-313 and 50-368 Arkansas Power & Light Corpany Mr. William Cavanaugh, III Vice President, Generation

'and Construction P. O. Box 551 Little Rock, Arkansas 72203

Dear Mr. Cavanaugh:

By letter dated April 30, 1979, you submitted Revision 2 to the Fire Protection Plan for Arkansas fiuclear One, Unit tio.1 ( Att0-1).

We have reviewed Revision 2 and find it to be acceptable except for two items identified in the enclosure. We request your response to our concerns in the enclosure within 30 days on receipt of this letter.

Additionally, your letter of April 30, 1979 only references AtiO-1 and its docket number. The fire Protection Plan should also be applied to AtiO-2. We request you place Revision 2 and subsequent changes on the AtiO-2 dr;ket as well as the A."0-1 docket.

fincerely, m

..O'/

g _!~/I'hi & sf Robert W. Reid, Chief Operating Reactors Branch #4 Division of C'perating Reactors

/^

f m/

/

wff i

John r. Stolz, ' Chief

/

Light Water Reactors Bfanch 41 Fvision of Project Management

Enclosure:

Questions cc w/ enclosure: See next page 490 187 0 SLD qgc130

V W

Arkansas Power & Light Company cc:

Phillip K. Lycr Esq.

House, Holms & Jewell 1550 Tower Building Little Rock, Arkansas 72201 Mr. David C. Trimble Manager, Licensing Arkansas Power & Light Company P. O. Box 551 Little Rock, Arkansas 72203 Mr. James P. O'Hanlon General Manager Arkansas Nuclear One P. O. Box 603 Russellville, Arkansas 72801 Mr. William Johnson U. S. Nuclear Regulatory Conn:ssion P. O. Box 2090 Russeliville, Arkansas 72801 Mr. Robert B. Borsun Babcock & Wilcox Nuclear Power Generation Division Suite 420, 7735 Old Georgetown Road Bethesda, Maryland 2001 Troy B. Conner, Jr., Esq.

Conner, Moore & Corber 1747 Pennsylvania Avenue,

'4.W.

Washington, D.C.

20006 Arkansas Polytechnic College Russellville, Arkansas 72801 490 188

,. s ENCLOSURE ARKANSA5 NUCLEAR ONE FIRE PROTECTION ACTION PLAN DOCKET NOS. 50-313, 363 1.

The Fire Protection Quality Assurance secticn (page 13) indicates that for inspecticns, tests, and audi ts related to fire protection, " applicable" cortions of tne QA Tcpical, Fire Protection Plan, and Tecnnical Specifications will be applied.

This conc.i tment is not clear.

The extent that Technical Specificati;ns apply to fire protection is clearly defined in the Technical Soeci fi ca ti on s.

Any portions of ne QA Topical cr Fire

?rotection Plan that will not be applied to fire :rotic.i:n inspection, test, or audit activities sncuid be clearly i:entified and justification provided for not using these.

If tre intent is to follow the QA Tcpical, Fire Protection Olan, an:

Technical Soecifications in performing fire protection inspec-tions, tests, and audits, then " applicable portions of" or

" applicable sections of" should be deleted from tne lead in sentence and sections 2., 3., and 4. of the Fire Protecticn Quality Assurance section.

2.

The last sentence of paragraoh 1.a in the Control of Combustibles section (cage 10) was changed' by Revisicn 2 to incorporate commitments made in the 7,F&L letter of June 29, 1973 in response to staff item 7d from tne meeting of May 24, 1978 Hcwever, the change to this sentence does not accurately reflect the commitment in the June 29, 1973 l e tte r.

This sentence should be changed to read:

"No comoustibles will be stored in fire zones with redundant safe shutdcwn circuitry and/or equiprent, no combustibles will be stored in other safety relatec

cnes, unless that zone is protected by a sprinkler systen."