yac PD A

g... %

UNITED STATES g

+

NUCLEAR REGULATORY COMMISSION y

3.,

p, E

W ASHINGTON, D. C. 20555 JJN 6 1979

%, *..../

Pocket No. 50-267 Mr. C. K. Millen, Senior Vice President Public Service Company of Colorado P. O. Box 840 Denver, Colorado 80201

Dear Mr. Millen:

SUBJECT:

FORT ST. VRAIN NUCLEAR GENERATING STATION AMENDMENT NO. 21 TO FACILITY OPERATING LICENSE NO. OPR-34 The Comissien has issued the enclosed Amendment No. 21 to Facility Operating License No. DPR-34 for the Fort St. Vrain Nuclear Generating Station in response to your applications for amendment dated December 11, 1978, Septenter 8,1978, April 2,1979, November 16, 1977 and October 5, 1978.

The amendment revised the Technical Specifications to:

(1) modify the fire protection system for the three room complex, the Auxiliary Electric Room, the 480 Volt Switchgear Room and the congested cable areas; this constitutes Stage III fire protection implementation; (2) convert the Interim Alternate Cooling method to the final Alternate Cooling (Method; (3) test the reactor building louver system on a quarterly basis; 4) eliminate the manual iso-lation of the high pressure helium supply from the helium circulator buffer supply header; and (5) add two firewater booster pumps to the firewater system to provide adequate capacity to operate a circulator water turbine and supply emergency cooling water for safe shutdown cooling.

A copy of the Safety Evaluation supporting this amendment and the related Federal Register hatice are also enclosed.

Sincerely, Y-wm William P. Gamill, Assistant Director for Standardization and Advanced Reactors Division of Project Management Office of Nuclear Reactor Regulation E: closures:

1.

Amendment No. El to DPR-34 2.

Safet.y Evaluation 3.

Federal Registcr Notice 358 268 cc:

See next page 7 9

'7 2 mC 6

0

C. K. Millen JUN 6 1979 cc: Bryant O'Donnell, Esquire Kelly, Stansfield and O'Donnell 990 Public Service Company Building Denver, Colcrado 80202 Director, Division of Planning Department of Local Affairs 615 Columbine Building 1845 Sherman Street Denver, Colorado 80203 Chairma,i, Board of County Comissioners of Weld County, Colorado Greeley, Colorado 80631 Regional Representative, Radiation Programs Environmental Protection Agency 1860 Lincoln Street Denver, Colorado 80203 James B. Graham, Manager Licensing and Regulation East Coast Office General Atomic Company 2021 K Street, N.W.

Suite 709 Washington, D. C.

20006 358 269