Forwards Suppl IE Bulletin 79-01A, Environ Qualification of Class IE Equipment (Deficiencies in Environ Qualification of Asco Solenoid Valves). Action Required
ML19246B942
Person / Time
Site: Zimmer
Issue date: 06/06/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Borgmann E
CINCINNATI GAS & ELECTRIC CO.
References
NUDOCS 7907190236
Download: ML19246B942 (1)


Text

PDR pa asc UNITEo sTATC';

NUCLEAR REGULATORY COMMISSION

's Pi REGION lli f

,a 799 ROOSEVELT RO AD e

D 4

GLEN ELLYN. ILLINOIS 60137

,o*

JUN 6 1979 Docket No. 50-358 Cincinnati Gas and Electric Company ATTN:

Mr. Earl A. Borgmann Vice President Engineering Services and Electric Production 139 East 4th Street Cincinnati, OH 45201 Gentlemen:

Enclosed is supplement IE Bulletin No.79-01A.

It requires action by you with regard to power reactor facilities with an operating license except for the 11 SEP plants which are listed in Enclosure 3.

This Bulletin is also being sent for information to the 11 SEP plants and all power reactor facilities with a construction permit. No action or written response is required for construction permit facilities or the 11 SEP plants.

Should you have questions regarding this Bulletin or the actions required of you, please contact this office.

Sincerely, O

h A

[JamesG.Keppler d Director

Enclosure:

IE Bulletin No.79-01A cc w/ encl:

Mr. J. R. Schott, Plant TIC Superintendent Harold W. Kohn, Power Central Files Siting Commission Director, NRR/DPM Citizens Against a Radioactive Director, NRR/ DOR Environment PDR Helen W. Evans, State of Local PDR Ohio NSIC 7907190236 343 i0y

U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPFCTION AND ENFORCEMENT

" REGION III June 6, 1979 IE Bulletin No. 79-OlA SUPPLEMENT NO.79-01A TO IE BULLETIN 79 ENVIRONMENTAL QUALIFICATION OF CLA'IS 1E EQUIPMENT (DEFICIENCIES IN THE ENVIR0hM2 ITAL QUALIFICATION OF ASCO SOLENCID VALVES)

Description of Circumstances:

Recently, a noncompliance r eport under 10 CFR Part 21 was received by the NRC r =pany, manufacturer of butterfly valves which are from the Henry Pratt c

installed in the primary containment at the Three Mile Island Unit 2 Nuclesr Station.

These butterfly valves are used for purge and exhaust purposes and are required to operate during accident conditions The report discusses the use of an unqualified solenoid valve for a safety-related valve function which requires operation under accident conditions. The solenoid valve in question is Catalogue No. HT-8331A45, manufactured by the Automatic Switch Company (ASCO) of Florham Park, New Jersey. This pilot valve is used to pilot control the pneumatic valve actuators which are installed on the containment ventila-tion butterfly valves at this facility.

The deficiency in these solenoid valves identified in the Part 21 Report concerns the parts made of acetal plastic material. The acetal disc holder asse=bly and bottom plug in the pilot valve asse=bly are stated by ASCO to have a maximum service limit of 400,000 Rad integrated dosage and 200 degrees F t e=p erature. According to ASCO, exposure of these acetal plastic parts to specified max 1=um environmental conditions may render the solenoid pilot valve inoperable which would cause the associated butterfly valve to malfunction.

Further investigation at ASCO by the NRC staff has revealed that the valve seals in most ASCO solenoid valves contain Buna "N" elastomer material, which reportedly has a maximum service limit of 7,000,000 Rad integrated desage and 180 degrees F te=nerature. The investigation further revealed that ASCO has available a line of qualified solenoid operated pilot valves (ASCO Catalogue No. NP-1) which have no plastic parts, utilize ethylene propylene or viton elastemers and have a centinuously energized operating life of four years, under normal ambient conditions up to 140 degrees F.

According to the manu-facturer, at the end of this period, the coil, manual operator (optional fea-tare) and all resilient parts must be replaced. These preventive maintenance instructions are specified in the installation and instruction bulletins which are provided to the purchaser with each shipment of solenoid valves.

The final items of concern identified during this investigation deals with the application of Class "A",

"B", or "F",

solenoid coils which are exposed to an accident environment.

In this regard, ASCO representatives stated that the 0 #

q90g 02 2Jpi ll fY

II Bulletin No.79-01A June 6, 1979 high te=perature coils identified as Cisss "HT" or "HB" are the only coils con-sidered suita le for service under accident condicians; whereas, Class "A",

"B",

anc "F" coils are not.

With, respect to the corrective =easures to be taken to resolve the above concerns, ASCO reco== ends the following:

1.

The parts of the solenoid valve made of acetal plastic =aterial should be replaced with similar parts made of metal which can be provided by ASCO.

2.

The valve seals and gaskets which are made of Buna "N" material should be replaced with either ethylene propylene or viten elasta=ers, considered by ASCO 0; suitable for the service intended.

3.

Review and determine that the coils of the solencid valves installed inside containment are Class "HT" or "EB" as required for high te=perature environ = ental conditions.

4.

Review and deter =ine that the solenoid enclosures installed inside contain-

=ent have st least a NEMA 4 enclosure rating.

5.

Establish a preventive maintenance program to assure replacement of those valve parts identified above in the time period reco== ended in the appro-priate ASCO valve bulletin.

6.

ASCO also stated that all unqualified soienoid valves inside contain=ent be retrofitted to qualified ASCO No. NP-i valves in lieu of the above.

7.

Questions fro = licensees to ASCO concerning corrective measures should reference both catalogue and serial nu=bers of each valve in question.

These nu=bers are sta= ped on the metal nameplate on each solenoid valve.

Action to be Taken by Licensees of all Power Reactor Facilities (except those 11 SEP Plants listed en Enclosure 3) with an Operating License:

1.

Deternine whether or not ASCO solenoid valves are used or planned for use in safety-related systems at your facility (ies).

2.

If such valves are used or planned for use, identify the safety syste=

involved and determine that:

(a) valves which could be subjectec to a LOCA environ =ect are qualified to that environ =ent.

Specifically that no parts made of acetal plastic or Buna "N" =aterials or Class "A",

"B",

or "F" solenoid coils are used in such valves; (b) a preventive =ain-tenance progra= is being conducted such that the colenoid coil, the manual operator (if applicable), and the resilient parts of the valve are being replaced in accordance with the ti=e period established by the marufacturer and docu=ented as the qualified life of the asse= bled ec=ponent.

fff

IE Bulletin No.79-01A June o, 1979 3.

All holders of operating licenses of power reactor facilities are obligated to meet the review and reporting require =ents established in previously issued IE Bulletin 79-01, regarding environmental qualifica--

tion of electrical equipment installed in their plants.

No additional written response to this Supplement IE Bulletin is required other than those responses described above. NRC inspectors will continue to monitor the licensees' progress in completing the requested action described above.

If additional information is required, contact the Director of the appropriate NRC Regional Office.

Approved by GAO, B180225 (R0072); clearan:e expires 7/31/80. Approval was given under a blanket clearance specifically for identified generic problers.

Enclosures:

1.

List of IE Bulletins Issued in the past 12 conths 2.

List of SEP Plants (11) 343 i 12

IE Bulletin No.79-01A June 6, 1979 LISTING OF IE BULLETINS ISSUED IN LAST T'ALVE MONTHS Bulletin Subject Date Issued Issued To No.

79-f2 Short Period Scra=s at 5/31/79 All CE EWK Facilities with an OL BWR Facilities 79-11 Faulty Overcurrent Trip 5/22/79 All Power Reactor Levice in Circuit Breakers Facilities with an OL or a CP for Zngineered Lafety Systens 79-10 Requalification Training 5/11/79 All Power Reactor Facilities with an OL Program Statistics 79-09 Failures of GE Type AK-2 4/17/79 All Power Reactor Circuit Breaker in Safety Facilities with an OL or CP Related Syste=s 79-08 Events Relevant to BWR 4/14/79 All BWR Power Reactor Reactors Identified During Facilities with an OL Three Mile Island Incident 79-07 Seismic Stress Analysis 4/14//9 All Power Reactor of Safety-Related Piping Facilities with at.

OL or CP 79-063 Review ot Operational 4/14/79 All Combustion Engineer-Errors and System Mis-ing Designed Pressurized align =ents Identified Water Power Reactor During the Three Mile Facilities with an Island Incident Operating Licensee 79-06A Review of Operational 4/18/79 All Pressuri:ed Water (Rev 1)

Errors and System Mis-Power Reactor Facilities alignments Identified of Westinghouse Design During the Three Mile with an OL Island Incident 79-06A Review of Operational 4/14/79 All Pressurf:ed Water Errors and System Mis-Power Reactor Facilities al.gnments Identified of Westinghouse Design During the Three Mile with an CL Island Incident Enclosure Page 1 of 3 hb

IE Bulletin No.79-01A June 6, 1979 LISTING OF IE BULLETINS ISSUED IN 1AST TWELVE MONTHS Bulletin Subject Date Issued Issued To No.

79-06 Review of Operational 4/11/79 All Pressurized Water Errors and System Mis-Power Reactors with an alignments Identified OL except B&W facilities During the Three Mile Island Incident 79-05A Nuclear Incident at 4/5/79 All B&W Power Reactor Three Mile Island Facilities with an OL 79-05 Nuclear Incident at

')

All Power Reactor Three Mile Island Facilities with an OL and CP 79-04 Iacorrect Waights for 3/30/79 All Power Reactor Swing Check Valves Facilities with an Manufactured by Velan OL or CP Engineering Corporation 79-03 Longitudinal Welda Defects 3/12/79 All Power Reactor In ASME SA-312 Type 304 Facilities with an Stainless Steel Pipe Spools OL or CP Manufactured by Youngstown Welding and Engineering Co.

79-02 Pipe Support Base Place 3/2/70 All Power Reactor Designs Using Concrete Facilities with an Expansion Anchor Bolts OL or CP 79-01 Environmental Qualification 2/8/79 All Power Reactor of Class IE Equipment Facilities with an OL or CP 78-14 Deterioration of Buna-N 12/19/78 All CE BWR facilities Component In ASCO with an OL or CP Solenoids 78-13 Failures in Source Heads 10/27/78 All general and of Kay-Ray, Inc., Cauges spscific licensees Bodels 7050, 7050B, 7051, with the subject 7051B, 7060, 7060B, 7061 Kay-Esy, Inc.

and 7061B gauges Encicsure Page 2 of 3 343 i14

IE Bulletin No.79-01A June 6, 1979 LISTING OF IE BULLETINS ISSUED IN LAST TVELVE MONTHS Bulletin Subject Date Issued Issued To No.78-12B Atypical Weld Material 3/19/79 All Power Reactor in Reactor Pressure Facilities with an Vessel Welds OL or CP 78-12A Atypical Weld Material 11/24/78 All Power Reactor in Reactor Pressure Facilities with an Vessel Welds OL or CP 78-12 Atypical Weld Material 9/29/78 All Power Reactor in Reactor Pressure Facilities with an Tessel Welds OL or CP 78-11 Examination of Mark I 7/21/78 BWR Power Reactor Contain=cnt Torus Welds Facilities for action:

Peach Bottcu 2 and 3, Quad Cities 1 and 2, Hatch 1, Monticello and Vermont Yankee 78-10 Bergen-Paterson Hydraulic 6/27/78 All BWR Power Reactor Shock Suppressor Accumulator Facilities with an Spring Coils OL or CP 78-09 BWR Drywell Leakage Paths 6/14/79 All BWR Power Reactor Associsted with Inadequate Facilities with an Drywell Closures OL or CP 78-08 Radiation Levels from Fuel 6/12/78 All Power and Research Element Transfer Tubes Reactor Facilities with a Fuel Element transfer tub + snd an OL 78-07 Protection afforded by 6/12/78 All Power Reactor Air-Line Respirators and Facilities with an OL, Supplied-Air Hoods all class E and F Research Reactors with an OL, all Fuel Cycle Facilities with an OL, and all Priority 1 Material Licensees Enclosure Page 3 of 3 l[ 7 llI

SEP Plants Plant Region Dresden 1 III Yankee Rowe I

a Big Rock Point III San Onofre 1 V

Haddam Neck I

Lacrosse III Oyster Creek I

R. E. Ginna I

Dresden 2 III Millstone I

Palisades III Enclosure Page 1 of I fb