Forwards IE Bulletin 79-01A, Environ Qualification of Class IE Equipment (Deficiencies in Environ Qualification of Asco Solenoid Valves). Action Required
ML19246B904
Person / Time
Site: Crane  
Issue date: 06/06/1979
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Herbein J
METROPOLITAN EDISON CO.
References
NUDOCS 7907190062
Download: ML19246B904 (1)


Text

p***E%q%

7%

8 UNITED STATES 8 h,#(

NUCluAR REGUL ATORY COMMISEION E

REGION I 3 J-

, [

631 PARK AVENUE S

e U

o KING OF PRUSSIA, PENNSYLVANI A 19406 June 6, 1973 Docket Nos. 50-289 50-320 Metropolitan Edison Company ATTN: Mr. J. G. Herbein Vice President - Generation P. O. Box 542 Reading, Pennsylvania 19640 Gc1tlemen:

Enclosed is supplement IE Bulletin 79-OlA.

It requires action by you with regard to power reactor facility (ies) with an operating license except for the 11 SEP (Systematic Evaluation Program) plants which are listed in Enclosure 3.

This Bulletin is also being sent for information to the 11 SEP plants and all power reactor facilities with a construction permit.

No action or written response is required for these two categories of facilities.

Should you have questiont regarding this Bulletin or the actions required of you, please contact this office.

Sincerely, h

n

__ Boyce H. Grier Director

Enclosures:

1.

IE Bulletin No.79-01A 2.

List of IE Bulletins Issued in Last Twelve Months 3.

List of SEP Plants (11) cc w/encls:

E. G. Wallace, Licensing Manager J. J. Barton, Project Manager R. C. Arnold, Vice President - Generation L. L. Lawyer, Manager - Generation Operations G. P. Miller, Manager - Generating Station - Nuclear J. L. Seelinger, Unit 1 Superintent:ent W. E. Potts, Unit 1 Superintendent - Technical Support J. B. Logan, Unit 2 Superintendent G. A. Kunder, Unit 2 Superintendent - Technical Support p

gOPj 9 I. R. Finfrock, Jr.

Mr. R. Conrad 0064J G. F. Trowbridge, Esquire Miss Mary V. Southard, Chainnan, L1tizent for a Sai'e Environment 3Al 346

ENCLOSURE 1 UNITED STATES NUCLEAR REGULATORY COMM' 10N WASHINGTON, D /. 20550 IE Bulletin No. 79-OlA Date: June 6, 1979 Page 1 of 3 SUPPLEMENT NO.79-01A TO IE BULLETIN 79 ENVIRONMENTAL QUALIFICATION OF CLASS 1E EQUIPMENT (DEFICIENCIES IN THE ENVIRONMENTAL QUALIFICATION OF ASCO SOLEN 0ID VALVES)

Description of Circumstances:

Recently, a noncompliance report under 10 CFR Part 21 was received by the NRC from the Henry Pratt Company, manufacturer of butterfly valves which are installed in the primary containment at the Three Mile Island Unit 2 Nuclear Station.

These butterfly valves are used for purge and exhaust purposes and are required to operate during accident conditions.

The report discusses the use of an unqualified solenoid valve for a safety-related valve function which requires operation under accident conditions.

The solencio valve in question is Catalogue No. HT-8351A45, manufactured by tne Automatic Switch Company (ASCO) of Florham Park, New Jersey. This pilot valve is used to pilot control the pneumatic valve actuatcrs which are installed on the containment ventilation butterfly valves at this facility.

The deficiency in these solenoid vaives identified in the Part 21 Report concerns the parts made of acetal plastic material.

The acetal disc holder assembly and bottom plug in the pilot valve assembly are stated by ASCO to have a maximum service limit of 400,000 Rad integrated dosage and 200 degrees F temperature.

According to ASCO, exposure of these acetal plastic parts to specified maximum environment >' conditions may render the solenoid pilot valve inoperable which would cause the associated butterfly valve to malfunction.

Further investigation at ASCO by the NRC staff has revealed that the valve seals in most ASCO solenoid valves contain Buna "N" elastomer material, which reportedly has a maximum service limit of 7,000,000 Rad integrated dosage and 180 degrees F temperature.

The investigation further revealed that ASCO has available a line of qualified solenoid operated pilot valves (ASCO Catalogue No. NP-1) which have no plastic parts, utilize ethylene propylene or viton elastomers and have a continuously energized on arating life of four years, under normal embient condition:.

up to 140 degrees F.

According to the manufacturer, at the end of this period, the coil, manual operator (optional featurc) and all resilient parts must be replaced.

These preventive maintenance instructions are specified in the installation and instruction bulletins which ere provided to the purchaser with each shipment of solenoid valves.

The final items of concern identified during this investigation deal with the application of Class "A", "B", or "F", solenoid coils which ere exposed to an accident environment.

In this regard, ASCO representatives stated that the 20070e0173 30

,A

IE Bulletin No. 79-OlA Date:

June 6,1979 Page 2 or 3 hiah temperaturc coils identified as Class "HT" or "HB" are the only coils con-sidered suitable

.c service under accident conditions; whereas, Class "A", "B",

and "F" coils are not.

With respect to the corrective measures to be taken to resolve the above concerns, ASCO recommends the following:

1.

The parts of the solenoid valve made of acetal plastic material should be replaced with similar parts made of metal which can be provided by ASCO.

2.

The valve seals and gaskets which are made of Bona "N" material should be replaced with either ethylene propylene or viton elastomers, considered by ASCO as suitaole for the service intended.

3.

Review and determine that the coils of the solenoid valves installed inside containment are Class "HT" or "HB" as required for high temperature environmental conditions.

4.

Review and determine that the solenoid enclosures installed inside contain-ment have at least a NEMA 4 enclosure rating.

5.

Establish a preventive maintenance program to assure replacement of those valve parts identified above in the time period recommended in the appro-priate ASCO valve bulletin.

6.

ASCO also stated that all unqualified solenoid valves inside containment be retrofitted to qualified ASCO No. NP-1 valves in lieu of the above.

7.

Questions from licensees to ASCO concerning carrective measures should reference both catalogue and serial numbers of each valve in question.

These numbers are stamped on the metal nameplate on each solenoid valve.

Action to be Taken by Licensees of all Power Reactor Facilities (ercept those 11 SEP Plants listed on Enclosure 3) with an Operating !.icense:

1.

Determine whether or not ASCO solenoid valves are used or planned foi use in safety-related systems at your facility (ies).

2.

If rouch valves are used or planned for use, identify the safety system involved and determine that:

(a) silves which could be subjected to a LOCA environment are qualified to that environment.

Specifically that no parts made of acetal plastic or Buna "N" materials or Class "A", "B",

or "F" solenoid coils are used in such valves; (b) a preventive main-tenance program is being conducted such that the solenoid coil, the manual erator (if applicable), and the resilient parts of the valve are being w

replaced in accordance with the tiene period established by the manufacturer and documented as the qualified life of the assembled component.

341 348

IE Bulletin No.79-01A Date:

June 6,1979 Page 3 of 3 3.

All holders of operating licenses of power reactor facilities are obligated to meet the review and reporting requirements established in previously issued IF Bulletin 79-01, regarding environmental qualifica-tion of electrical equipment installed in their plants.

No additional written response to this Supplement IE Bulletin is required other than those responses described above.

NRC inspector:;-will continue to monitor the licensees' progress in completing the requested action described above. If additional information is required, contact the Director of the appropriate NRC Regional Office.

Approved by GAO, B180225 (R0072); clearance expires 7/31/80.

Approval was given under a blanket clearance specifically for identified generic problems.

7d1 349

IE Bulletin Na. 79-01 A Date:

June 6, 19/9 Page 1 of 5 ENCLOSURE 2 LISTING OF IE BULLETINS ISSUED IN LAST TWELVE MCNTHS Bulletin Sr ject Date Issued Issued To No.

78-07 Protection afforded 6/12/78 All Power Reactor by Air-Line Respirators Facilities with an and Suppiled-Air Hoods CL, all class E and F Research Reactcrs with an OL, all Fuel Cycle Facilities with an OL, and all Priority I Material Licensees 78-08 Radiation Levels from 6/12/78 All Power, Test and Fuel Element Transfer Research Reactor Tubes Facilities with an OL having Fuel Element Transfer Tubes 78-09 BWR Drywell Leakage 6/14/78 All BWR Power Paths Associated with Reactor Facilities Inadequate Drywell with an OL (for action)

Closures or CP (for information) 78-10 Bergen-Paterson 6/27/78 All BWR Power Reactor Hydraulic Shock Facilities with Suppressor Accumulator an OL or CP Spring Coils 78-11 Examination of Mark I 7/24/78 BWR Power Reactor Containment Torus Facilities with an OL Welds for action:

Peach Bottom 2 and 3, Quad Cities 1 and 2, Hatch 1, Monticello and Vermont Yankee.

All other BWR Power Reactor Facilities with an OL for information 341 350

IE Bulletin No.79-01A Date:

June 6, 1979 Page 2 of 5 LISTING OF IE BULLETINS ISSUED IN LAST TWELVE MONTHS (CN!TINUED)

Bulletin Subject Date Issued Issued To No.

78-12 Atypical Weld Material 9/29/78 All Power Reactor in Reactor Pressure Facilities with an Vessel Welds OL or CP 78-12A Atypical Weld Material 11/24/78 All Power Reactor in Reactor Pressure Facilities with an Vessel Welds OL or CP 78-12B Atypical Weld Material 3/19/79 All Power Reactor in Reactor Pressure Facilities with an Vessel Welds OL or CP 78-13 Failures In Source Heads 10/27/78 All General and of Kay-Ray, Inc., Gauges Specific Licensees Models 7050, 70508, 7051, with the subject 7051B, 7060, 70608, 7061 Kay-Ray, Inc.

and 7061B Gauges 78-14 Deterioration of Buna-N 12/19/78 All GE BWR Faci-Components In ASCO lities with an OL Solenoids (for action), and all other Power Reactor Facilities with an OL or CP (for information) 79-01 Envirar-,tal 0 dl# f-2/8/79 All Power Reactor icatir

? Class IE Facilities with an OL, Equi pi..en t except the 11 Systematic Evaluation Program Plants (for action), and all other Power Reactor Facilities with an OL or CP (For Information) 79-02 Pipe Support Base Plate 3/8/79 All Power Reactor Design Using Concrete Facilities with an OL Expansion Anchor Bolts or CP 341 351 IE Bulletin No.79-01A Date:

June 6, 1979 Page 3 of 5 LISTING 0F IE BULLETINS ISSUED IN LAST TWELVE MONTHS (CONTINUED)

Bulletin Subject Date Issued Issued to No.

79-03 Longitudinal Weld Defects 3/12/79 All Power Reactor in ASME SA-312 Type Facilities with 304 Stainless Steel Pipe an OL or CP Spools Manufactured by Youngstown Welding and Engineering Correany 79-04 Incorrect Weights for 3/30/79 All Power Reactor Swing Check Valves Facilities with on Manufactured by Vehn OL or CP Engineering Corporation 79-05 Nuclear Incident at 4/1/79 All Babcock and Three Mile Island Wilcox Power Reactor Facilities with an OL, Except Three Mile Island 1 and 2 (For Action),

and All Other Power Reactor Facilities With an OL or CP (For In1 Formation)79-05A Nuclear Incident at 4/5/79 Same c 79-05 Three Mile Island -

Supplement 79-06 Review of Operational 4/11/79 All Pressurized Water Errors and System Mis-Power Reactor Facil-alignments Identified ities with an OL Except During the Three Mile B&W Facilities (For Incident Action), All Other Power Reactor Facil-ities with an OL or CP (For Information) 341 352

IE Bulletin No. 79-01 A Date: June 6, 1979 Page 4 of 5 LISTING 0F IE BULLETINS ISSUED IN LAST TWELVE MONTHS (CONTINUED)

Bulletin Subject Date Issued Issued to No.79-06A Same Title as 79-06 4/14/79 All Westinghouse Designed Pressurized Power Reactor Facil-itie5 with an OL (For Action), and All Other Power Reactor Facilities with an C' or CP (For Information)79-06A S..ne Title as 79-06 4/18/79 All Westinghouse (Revision 1)

Designed Pressurized Power Reactor Facil-ities with an OL (For Action), and All Other Power Recctor Facilities with an OL or CP (For Information)79-06B Same Title as 79-06 4/14/79 All Combustion Engineering Designed Pressurized Power Reactor Facilities with an OL (For Action), and All Other Power Reactor Facilities with an OL or CP (For Information) 79-07 Seismic Stress Analysis 4/14/79 All Power Reactor of Safety-Related Piping Facilities with an OL or CP 341 353

IE Bulletin No.79-01A Date:

June 6, 1979 Page 5 of 5 LISTING OF IE BULLETINS ISSUED IN LAST TWELVE MONTHS (CONTINUED)

Bulletin Subject Date Issued Issued to No.

79-08 Events Relevant to 4/14/79 All BWR Power Boiling Water Power Reactor Facilities Reactors Identified with an OL (For During Three Mile Action), All Other Island Incident Power Reactor Facil-ities with an OL or CP (For Information) 79-09 Failures of GE Type 4/17/79 All Power Reactor AK-2 Type Circuit Facilities with an Breaker in Safety OL or CP Related Systems 79-10 Requalification Training 5/11/79 All Power Reactor Program Statistics Facilities with an OL 79-11 Fault, dvercurrent Trip 5/22/79 All Power Reactor Device in Circuit Breakers Facilities with an for Engineered Safety OL or CP Systems 79-12 Short Period Scrams at 5/31 /79 All GE BWR Facilities BWR Facilities with an OL 341 354

ENCLOSURE 3 SEP Plants Plant Region Dresden 1 III Yankee Rowe I

Big Rock Point III San Onofre 1 V

Haddam Neck I

Lacrosse III Oyster Creek I

R. E. Ginna I

Dresden 2 III Millstone 1 I

Palisares III

\\

341 355