ML19246B220
| ML19246B220 | |
| Person / Time | |
|---|---|
| Site: | Zimmer |
| Issue date: | 06/25/1979 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Borgmann E CINCINNATI GAS & ELECTRIC CO. |
| References | |
| NUDOCS 7907120693 | |
| Download: ML19246B220 (1) | |
Text
g#
'g, UNITED STATES
- yy
, 'g N L'C L E A R REGULATORY COMMISSION 3 f( g; 7 e g
REGION W g-(
799 noose ve tT sono
%~
4 G L E N E L L Y N. IL LINOIS 60137 June 25, 1979 Docket No. 50-358 Cincinnati Gas and Electric Company ATTN:
Mr. Ec.rl A. Borgmann Vice President Engineering Services and Electric Production 139 Fast 4th Street Cincinnati, OH 45201 Gentlemen:
The enclosed lE Bulletin No. 79-13 is forwarded to you for information.
No written response is required.
If you desire additional information regarding this matter, please contact this office.
Sincerely,
,r. James G. Keppler Director
Enclosures:
- 2. Listing of lE Bulletins 1ssued in Last 12 Months cc w/ encls:
Mr. J. R.
Schott, Plant Superintendent Central Files Director, NRR/ DPM Dir- ;or, NRR/ DOR PDR Local PDR NSIC TIC Harold W. Kohn, Ohio Power Siting Commission Citizens Against a Radioactive Environment
}5
_., f
)
d' s,
g
/
7007120 69)
U.S. NUCLEAR REGULAT0nY COMMISSION 0FFICE OF INSPECTION AND ENFORCEMENT REGION Ill June 25, 1979 IE Bulletin No. 79-13 CRACKING IN FEEDWATER SYSTEM PIPING Description of Circumstances:
On May 20, 1979, Indiana and Michigan Power Company notified the NRC of cracking in two feedwater lines at their D. C. Cook Unit 2 facility. The cracking was discovered following a shutdown on May 19 to investigate leakage inside containment. Leaking circumferential cracks were identified in the 16-inch feedwater elbows adjacent to two steam generator nozzle elbow welds.
Subsequent radiographic examination revealed crack indications in all eight steam generator feedwater lines at this location on both Units 1 and 2.
On May 25, 1979, a letter was sent to all PWR licensees by the Office of Nuclear Reactor Regulation which informed licensees of the D. C. Cook failures and requested specific information on feedwater system design, fabrication, inspection and operating histories. To further explore the generic nature of the cracking problem, the Office of Inspection and Enforcement requested licensees of PWR plants in current outages to immediately conduct volumetric examination of certain feedwater piping welds.
As a result of these actions, several other licensees with Westinghouse steam geneJators reported crack indications. Southern California Edison reported on June 5, 1979, that radiographic examination revealed indications of cracking in feedwater nozzle-to-piping welds on two of three steam generators of San Onofre Unit 1.
On June 15, 1979, Carolina Power and Light reported that radiography showed crack indications in similar locations at their H. B. Robinson Unit 2.
Duquesne Power and Light confirmed on June 18, 1979, that radiography has shown cracking in their Beaver Valley Unit 1 feedwater piping to vesscl nozzle veld. Public Service Electric and Gas Company reported on June 20, 1979 that Salem Unit 1 also has crack indications. Wisconsin Public Service company decided on June 20, 1979 to cut out a feedwater nozzle-to-pipe weld which contained questionable indication, for metallurgical examination. As of June 22, 1979 and since May 25, 1979 seven other PWR facilities have inspected the feedwater nozzle-to-pipe welds without finding cracking indications.
The feedwater nozzle-to-pipe configurations for D.C. Cook and for San Onofre are shown on the attached figures 1 and 2.