7.h-
~ - ~,
Jersey Central Power & Light Company J ( ', j " f.3 {^ u,,' -
f
{
Wd son A.ent at Punch BcM Road 3
4-Morr s'o.sn. Ne.v Jersey 07960 w.
(201).:55e?00 File: 2421.13
- ay 29, 1979 Mr. Boyce H.
Grier, Director Office of Inspection & Enforcement Region I U.S.
Muclear Regulatory Cor. mission 631 Park Avenue King of Prussia, PA 19406
Dear Mr. Grier:
SUBJECT:
FORKED RIVER NUCLEAR STATION (FRNS)
LICENSE NUMBER CPPR-96 DOCKET NUMBER 50-363 I&E BULLETIN 79-03 This letter is in response to I&E Bulletin 79-0 concerning weld defects in 304 or 312 stal
..c st eel pipe apool s manu f ac tured by Youngstown Welding and Engineering Company.
A review of our records indicate that stainless steel welded pipe spools oinufactured by Youngstown dolding and Engineering r~mpany were used for containment penetrations M-43 and M-44.
The spools, ahich were used for the containment sump suction lines, are 24 inch in diareter and 3/8 inch wall thickness, designed for
'00 psig/250 F.
Defects were discovered in the subject spools as a rcsult of CA inspections performed before the spools were placed.
As a rm ult of the discovery of these defects, the welds were 1001 radiographed and all identi.fied defects ee re rer:ov ed and rcs aired by zelding.
Seal welled piping is not now planned for future use at
- '; S.
If, icwever, s.:am olded piping is used in 'he future, the application will be eraluated and aporopriate acfion ( inc l u :l i n g radi+araphs, if necessary) will be taken.
If you have any questions concerning the L;ve, olease do not ",nitate to contact me.
cry truly
- m ors, 504 1"
r' an R.
'in;1 ok,
.ir.
'fico I(
- i d t -nt
.3b 0'
ctor of In 11 r J < > n, DC
(
i 790go805
'