ML19242B166
| ML19242B166 | |
| Person / Time | |
|---|---|
| Site: | FitzPatrick |
| Issue date: | 08/03/1979 |
| From: | Zufelt E POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK |
| To: | |
| Shared Package | |
| ML19242B161 | List: |
| References | |
| NUDOCS 7908070599 | |
| Download: ML19242B166 (13) | |
Text
-
OPERATING DATA REPORT 50-333 DOCKET NO.
DATE Aug. 1979 C051PLETED BY E. Zufelt TELEPliONE (315)342-3840 OPERATING STATUS Fit:: Patrick Notes
- 1. Unit Name:
790701 - 790731
- 2. Reporting Period:
2436
- 3. Licensed Thermal Power (5!Wt):
883
- 4. Nameplate Rating (Gross MWe):
821
- 5. D. sign Electrical Rating (Net StWe):
830
- 6. Maximum Dependable Capacity (Gross MWe):
800
- 7. Maximum Dependable Capacity (Net MWe):
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
- 9. Power Level To Which Restricted,If Any (Net Mbe):
Plar.t in cold shutdown condition in accordance
- 10. Reasons For Restriction;,1f Any:
with NRC "Show Cause" order of March 13, 1979.
This Month Yr. to Date Cumularise 744 5087 35160
- 11. Ilours In Reporting Period 0
1767.3 23829.5
- 12. Number Of flours Reactor Was Critical 0
0
- 13. Reactor Resene Shutdown llours O
_,_ 1767.3 23054.4
- 14. Ilours Generator On.Line 0
- 15. Unit Resene Shu:down Ifours 0
0 0
- 16. Gross Thermal Energy Generated (MWil) 0 3626160 45640308 0
1235720 15530590
- 17. Gross Elec:rical Energy Generated (MWil) 0 1198435 15024420
- 18. Net Electrical Energy Generated (MWil) 0 34.7 %
65.6 %
- 19. Unit Service Factor 0
34.7 %
65.6 t
- 20. Unit Availability Factor 0
29.4 %
59.7 %
- 21. Unit Capacity Factor (Using MDC Net) 0 28.7 %
52.0 %
- 22. Unit Capacity Factor (Using DER Net)
- 23. Unit Forced Outage Rate 100%
65.3 %
20.3 %
- 24. Shutdowns Sci eduled Oser Next 6 Months (T pe. Date,and Duration of EachL 3
None
[
[
3 Unknown - Pending completion '~
- 25. If Shut Down At End Of Report Period, Estimated Date of Startup: of pipe stress reanalvsis
- 26. Units in Test Status (Prior to Commercial Operation):
Forecr '
Achiesed INITIA L CRITICALITY C91
'OO V
/
U
s L
INITI \\ L ELECTRICITY COMMERCIAL OPER ATION
~
=.
'79 0807 0 Nf
AVERAGE DAILY UNIT POWER LEVEL 50-333 DOCKET NO.
UNIT JAFNPP DATE Aug. 1979 COMPLETED BY E. Zufe1t TELEPl!ONE (315)342-3840 MON 111 July 1979 DAY AVER AGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (M We-Net )
(MWe-Net) 1 0
37 0
2 0
is 0
3 0
39 0
4 0
20 0
5 0
0 21 6
0 0
22 7
0 23 0
8 0
0 24 9
0 0
25 10 0
0 26 11 0
27 0-12 0
0 28 13 0
0 29 14 0
30 0
15 0
0 33 16 0
Surraa ry :
Unit remains in cold shutdown condition in accordance with the NRC "Show Cause" order of March 13, 1979.
,C7 g
- ) J '
3)l
UNIT SilUTDOWNS AND POWER REDUCTIONS DOCKET NO.
50-333 UNIT N AME
'l A 'N' P DA.'E Aug. 1979 REPORT MONTil July 1979 COMPLETED BY E.
Lufe1t TELEPilONE (315)342,3840 I
cm t-~,
W C J q
=_
ri 3
-n :
S*
L) ',
Ee
,E, gt Cau: & Corrective c
o o
N. i-Date g
3g
.3 g y Event
- ?
o S. 3 Action to 3
$E 5
j5 Report n (N C Prevent Recurrence C
5 790315 F
744 D
4 79-014 ZZ ZZZZZZ Continuing re-evaluation of stress calculations and making modifica-tions as required.
(Cumulative hours to date - 3319.7)
I 2
3 4
IL Foned Reason:
Method :
Ex!abit G. inst ructions S: Sshedofed A-Equipment Failure (Explain) 1 Manual for Preparation of Data Il Maintenance of Test 2-Manual Scram.
Entry Sheels for Licensee C-Refueling 3-Automatic Scram.
Esent Report (LER) File (NUREG-D Regulatory Restriction 4 Other (Explain) 0161)
E Operator Training & License Examination F-Ad minist ra t iv e 5
G-Operational Error (Explain)
Exhibit I - Same Source il-Othe r ( E xplain)
@[4 JAMES A. FITZPATRICK NUCLEAR POWER PLANT p
to Maintenance Summary d
July 1979 - I f C 4
n
.4 O
Work Request #
rause of Results of Action taken to Repair Date System 1
ted Component #
Malfunction Malfunction Preclude Time Pecurrence (flours) 12548 7/9/79 03 03-PS-06 N/A N/A N/A SIL-283 10 2387 Intermittent Performed 7/11/79 07 1101 "D"
~~
OPS Unknown llal f Scrams F-ISP-7-1 1
2341 i"
7/11/79 07 Riol ll OPS Unknown Alarm Found OK 3
1787 Check di.erinin-7/21/79 07 SIG1 "i.B,C" IfC N/A N/A ator voltages 20 i
2173 7/21/79 07 I IDI "J" OPS Unknown Downc 11e Found OK i
2248 INp-7,2 7/20/79 07 SIO! "D" OP3 Noise fligh Readings ISP-7-2 20 2379 IMP-7.2 7/20/79 07 SIO! "D" OPS Noise Short Period ISP-7-2 20 2159 Faulty attenuator Replaced card 7/27/79 07 1101 "fl" OPS card Downscale IMP-7.3 4
1803 Alarm Replaced K2 8
7/?3/79 In i n-I s-l oc H '-
nos 9,a pol,y 1623 7/20/79 11 11-PI-53 OPS Plugted snubber No Reading Replaced snubber 3
2386 Tightened 7/5/79 13 13-TS-102C OPS Lo y cont;ection Alarm c n., n n e, + ; n, 20 235S Tightened 7/11/79 13 13-TS-102C OPS Loose connection Alarm connection
Ln BQ
((
JAMES A. FITZPATRICK NUCLEAR POWER DLANT m
m Maintenance Summary
'J July 1979 - ISC N
LO r 41 qu st #
Cause of Results of Action taken to Repair Date System llow Detected Comp >nent #
Malfunction Malfunction Preclude
. Time Recurrence (llours) 7;oS 7/16/79 99 Door 217 SEC Loose Latch Alarms Repaired latch 16 12222 Faulty Replaced QS02 7/23/79 99
- 4 Monitor SEC Transistor Poor Picture 6 filter 16 289 Installed 6 hookel1 7/23/79 99 Mini-Computer SEC N/A N/A up card readers 2
862 Repaired 7/23/7P 99 X-Ray SEC Age / Drift Poor Picture Adjusted ll.V.
24 897 7/23/79 99 Camera #2 SEC Drift Poor Picture Adjus.ed 8
1084 7/23/79 99 Camera #2/#3 SEC Age / Drift Poor Pictures Repaired 8
1997 7/23/79 99 Computer SEC N/A N/A Filter Maint.
1 f
e W
JAMES A. FITZPAi AICK NUCLEAR PONER PLANT g
g D
y Maintenance Summary oj July 1979-I6C r\\
ni cy
{Lomponent rk Request #
Cause of Results of Action taken to Repair
[hte System llow Detected Malfunction Malfunction Preclude Time Recurrence (flours) 2406 7/5/79 17 17-RIS-458B OPS h'a t e r No Indivition Dried out 4
2333 7/1(/79 17 17-RM-350 OPS Drift Failed ST decorder cal.
2 2264 7/19/79 17 17-RM-251D OPS Drift Blown Fuse F-ISP-64-1 13 2230 Bypass Valve 7/9 /79 20 20-FT-354 IGC Age Bad ReplaccI valve 4
2265 Incorrect 7/24/79 27 2 7-111 - 101 B OPS Drift Indication Calibrate 24 1089 7/5/79 99 Micro-raves SLC Drift No A l a ri..
Adjusted 16 1095 7/5/79 99 IAL-101 SEC Unknown Alarm Found ok 1
1092 7/9/:9 99 Door 217 SEC Bad Door Latch Alarm Replaced Latch 32 1085 7/16/~9 99 Printer Console SFC Unknown Spurious Alarm Found ok 2
1088 Difference in Air Adjusted 7/16/79 99 Door 314 SEC Press. MG Room /
Alarm Time Delay 16 Fan Room 1945 Alarm will 7/16/79 99 Friskem SEC Drift
reset Calibrate 6
1946 Replaced board 7/16/79 99 Door 311 SEC Age Alarm in #3 conc.
32
f'*7 POWER AUTHORITY OF THE STATE OF WEW YORK JAMES A.
FITZPATRICK NUCLEAR POWER PLANT
,7 m
N Safety Related Electrical f, Mechanical Maintenance Summary NJ g
WORK REQUEST #
REPAIR DATE SYSTEbl Il0W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONENT #
110URS 27 Jun 34 1546 N/A NRC Bulletin 79-02 Modified PFSK-34u 245':
PFSK-34B 21 Jun 46 1309 N/A NRC Bulletin 79-02 Repaired per MP'l-15 36 1146-197 20 Jun 10 12785 OPS Air Operators do not work Rebuild air operators 227 10-A0V-68 afb i
2 July 71 1880 ST N/A Cleaned LPCI battery rooms and 160
_ Bat-3A,3B performed PM on bnttery jar 3.
Also retorqued all connectors.
29 Jun 13 1924 N/A NRC Bulletin 79-02 Installed new support 463'i PFSK-1047 30. Inn 10 1272 OPS Check valve noisy Replaced valve internals 310 RllR-420 __
29.Iun 10 1318 Visual Loose anchor bolts Repaired per MPT-15 227'i fl10-476 21 Jun 76 1429 Visual Base plate away from wall Repaired per MPT-15 114 1176-47
POWER AUT110RITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR PONtR PLANT Safety Related Electrical f, Mechanical Maintenance Summary r
(b CNJ i
WORK REQUEST ti IEPAIR DATli SYSTEM Il0N DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME
{
COMPONENT ff 110URS m
5 Jul 10 1493 Visual Anchor bolts not Repaired per MPT-15 40 1110-114 tightened 21 Jun 46 1431 Visual llase plate from wall and Repaired per MPT-15 194'.s 114 6-184 f, 196 one anchor bolt redrilled g
i_n m
3 Jul 23 1767 Visual Anchors pulled out Repaired per MPT-15 105 1123-25 excessively on proof load test cd 1
27 Jun 46 1308 Visual Anchor bolts installed Installed new base plate 166 114 6 - 3 at an angle 3 Jul 10 1669 N/A NRC llulletin 79-02 Replaced existing baseplate 480';
1110-532 fasteners 9 Jul 10 1676 Visual Anchor bolt loose Inspecter per MPT-15 44 1110-537 2 Jun 10 1498 Visual Anchor bolt pulled loose Repaired per MPT-15 116 1110-127 from concrete 9 Jul 02 11910 OPS Rack valve has seat Replaced valve 8
02-1)l'I S-1 I SC leakage Low Side Rack Valve
POWER AUT:10RITY OF Tile STATE OF NEh' YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT Safety Related Electrical 6 Mechanical Maintenance Summary
%{
WORK REQUEST #
REPAIR DATE.
SYSTFht 110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONENT #
IIOURS h
13 Jul 19 1776 Visual NRC Bulletin 79-02 Modified 1119-229 91 1119-229 u.
17 Jul 10 1756 Visual NRC Bulletin 79-02 P.cpaired 1110-531 35815 1110-531 LO 17 Jul 10 1764 Visual NRC Bulletin 79-02 Repaired 1110-232 6 615 1110-232 J3 QJ u,
16 Jul 10 1841 Visual NRC Bulletin 79-02 Modifi ed 1110-225 151 1110-225 17 Jul 10 2232 Visual NRC Bulletin 79-02 Repaired 1110-545 58 1110-545 17 Jul 23 1369 Visual NRC Bulletin 79-02 Repaired 1123-24 260 1123-24 18 Jul 29 1545 Visual NRC Bulletin 79-02 Modified 1129-149 26015 1129-149 19 Jul 23 1373 Visual Loose bolt in pipe clamp Repaired 1123-2 2
112 3 - 2 9
PONER AUTHORITY OF THE STATE OF NEN YORK JAh!ES A.
FITZPATRICK NUCLEAR POWER PLANT S fety Related Electrical 6 b!echanical 5faintenance Summary O'
7
'NJ WORK REQUEST If IGPAIR
"~
DATE.
SYSTE31 ll0K DETECTED CAUSE OF 51ALFUNrTION ACTION TAKEN TO PIECLUDE RECURRENCE TIB!E
^j COntPONENT 4 d'
110URS 10 Jul 10 1757 Visual ll10-232A repair Repaired per F1PT-15 166 fil0-232A 10 Jul 29 1772 Visual Fasteners broken during Replaced fastenei s C
44S$
H29-347B inspection
'O 10 Jul 12 1905 Visual Fastener broken during Replaced fasteners
'f 272 PFSK-1040 inspection 9 Jul 29 1667 Visual NRC bulletin 79-02 Ifodified PFSK-1135A 467 PFSK-1135A 11 Jul 10 1544 N/A NRC Bulletin 79-02 h!odified 1110-213 168 1110-213 10 Jul 23 2363 OPS blisalignment of h!CC Aligned breaker operator 1
>!OV-57, P-140 breaker operator with breaker switch 9 Jul 23 2332 h!aint Improper reinstallation Replaced motor and corrected torque 16 b!OV-17 of valve operator torque switch installation switch following Ph!
caused motor to fail during post Ph! testing
POWER AUTil0RITY OF TIIE STATE OF NEW YORK JAMES A. FITZPATP.ICK NUCLEAR POWER PLANT Safety Related Electrical 6 Mechanical Maintenance Suminary L.3 C3 o
WORK REQUEST #
REPAIR DATE SYSTEM COMPONENT #
110N DETECTED CAUSF 0F MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME Il0VRS y
r>
h 12 Jul 12 2246 N/A NRC Bulletin 79-02 Modified 1112-86 151 1112-86 j-n, 14 Jul 19 1774 N/A NRC Bulletin 79-02 Modified h19-230 94 1119-230 1
14 Jul 10 1900 N/A Insulation removal for Remo.-d G reinstalled insulation 47 Il10-42A inspection 14 Jul 29 1542 Visual NRC Bulletin 79-02 Modified 1129-150 359 1129-150 13 Jul 02 1541 Visual NRC Bulletin 79-02 Modified PFSK-1234 60 PFSK-1254 14 Jul 10 2241 N/A Insulation removal for Removed 6 reinstalled insulation 2
1110-145 inspection 16 Jul 46 2397 Visual NRC P1211ctin 79-02 Repaired PFSK-1100 14 0's PFSK-1100 16 Jul 46 2398 Visual NRC Bulletin 79-02 Repaired PFSK-1101 8'4!1 PFSK-1101 _
h
POWER AUT110RITY OF Tile STATE OF NEW YORK JAMES A.
FITZPATRICK NUCLEAR POWER PLANT Safety Related Elcetrical G Mechanical ;aintenance Summary CD m
WORK REQUEST h REPAIR DATE.
SYSTEM COMPONENT #
!!OS DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME 110URS
~
N tl' 20 Jul 14 2223 N/A Insulation removal fo r Removed G reinstalled insulation 78 1114-46 inspection 20 Jul 46 2224 N/A Insulation removal for Removed G reinstalled insulation 34 1146-37 inspection 20 Jul 46 2225 N/A Insulation removal for Removed G reinstalled insulation 37 1146-36 inspection D J 1
17 Jul 27 1808 Visual Flange gasket leak Replace gasket F-6B Q
19 Jul 66 1810 OPS Clean unit cooler Cleaned strainers G flushed line y 32 UC-22A-K Y-strainers tr) 19 Jul 10 1799 Clean strainer Cleaned strainer 12 OPS S-5A 14 Jul 10 2371 Visuil Baseplate hole oversize Repaired S-5B hanger 20 S-5B 21 Jul 29
_1531 Visual NRC Bulletin 79-02 Modified 1129-213 4'7 1129-213
POWER AUTf!ORITY OF THE STATE OF NEW YORK JAMES A.
FITZPATRICK NUCLEAP. POWER PLANT Safety Related Electrical 6 Mechanical Maintenance Summary WORK REQUEST #
REPAIR DATE.
SYSTEh!
IION DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONENT #
Il0URS g
C.J 21 Jul 29 1777 Visual NRC Bulletin 79-02 Modified PTSK-1270 251 C
m boI E
20 Jul 12 1768 Visual Anchor bolt loose Repaired 2112-89 1
122's y,
h12-89
,.q DJ 41 0 21 Jul 14 1751 Visual NRC Bulletin 79-02 Modified II14-42A 410 fl14-42A 20 Jul 14 1908 Visual NRC Bulletin 79-02 Modified 1114-45 198 1114-45
.i 24 Jul 76 2153 Special Upon pump start, Control Removed spare contact spring 3
P-2 Testing Room did not receive assembly because it is not needed running light or annun-ciator.
Spare contact in auxiliary relay contact was jamming.
.