ML19242A166
| ML19242A166 | |
| Person / Time | |
|---|---|
| Site: | Point Beach |
| Issue date: | 07/13/1979 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Burstein S WISCONSIN ELECTRIC POWER CO. |
| References | |
| NUDOCS 7907310419 | |
| Download: ML19242A166 (1) | |
Text
..__ _ -
gp REG
[g
'o UNITED STATES E '}*, r ff' 'g NUCLEAR REGULATORY COMMISSION PDR
- .g
'"(-I[
799 ROOSEVE LT ROAD J'
c REGION ill 2
I 0,
f.
4
'N
[
GLEN E L LYN, f L LINOIS 60137 JUL 131979 i
Docket Nc. 50-266 Docket No. 50-301 Wisconsin Electric Power Company ATTN:
Mr. Sol Burstein Executive Vice President Power Plants 231 West Michigan Milwaukee, W1 53201 2
Gentlemen:
The enclosci IE Circular No. 79-13, is forwarded to you for infor-
- : tion.
Na "r.
- en response is required.
Should you have any questions related to ur understanding of this matter, please contact this office.
i Sincerely,
)
James G. Yeppler 2
Director
[
Enclosure:
IE Circular No. 79-13 4
cc w/ enc 1:
1 Mr. G. A. Reed, Plant 1
Manager l
Central Files Director, NER/DPM Director, JRR/ EOR C. M. Tremmel, ORB /NRR PDP Local PDR NSIC TIC Sandra A. Bast, Lakeshore Citizens for Safe Energy 3
i i
-9,
.37 i
s
]
7907210 #/7
U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT REGION III July 13, 1979 IE Circular No. 79-13 REPLACEMENT OF DIESEL FIRE PUMP STARTING CONTACTORS 1
Description of Circumstances:
On May 28, 1978, the Diesel Fire Pump failed to start remetely at Davis-Besse, Unit 1 facility operated by Toledo Edison Company. The cause for failure was defective starting contactors. A subsequent investigation into the cause of a aisilar failure on January 18, 1978, at Commonwealth Edison Company's Dresden 2/3 Diesel Fire Pump identified a generic problem with Cu== ins Indus-trial Fire Pump Engines.
Discussion:
The investigation revealed that Cu== ins Engine Company issued a Service / Parts Topics No. 74T 13-3A announcing new components available for Industrial Fire Pumps (NH-220-1F, N-855-F, N-855-F1, NT-855-F2 series engines) to improve operation of inline 6 cylinder Industrial Fire Pump Engines.
In this topic, Cummins recom= ends that when replacing the 118848 magnetic switch and 199573 DC relay contactor, use the new 217588 magnetic switch. The new design component has a 6 ampere draw whereas the old combination has approximately 3 amperes draw. Davis Besse and Dresden sites have implemented the corrective action recoc= ended by Cu= mins.
Recommended Actions for Licensees' Consideration:
All holders of operating licenses or construction peru.its shoulf be aware of the potential problem of the type discussed above.
Because of the generic implications in this matter, it recom= ended that both licensees of operating facilities and holders of conet ion permits conduct a revie-to determine if the above diesel fire pu=p <
.nes are in use or planned for use at your facility (ies).
If these engines are in use or planned for use, determine if the Cummins type 118848 Magnetic Switch and 199573 DC relay contactors are also employed.
For those engines which have these components, develop a pro-gram for their replacemant with the new 217588 Magnetic Switch.
No written response to this Circular is required.
If you require additional information regarding these matters, contact the Director of the appropriate NRC Regional Office.
~.
Q
[lDUPLICATEDOCUMENT
Enclosures:
1.
Cummins Service / Parts Topics (d
No.
74 T 13-13A.
] Entire document previously entered 2.
List of IE Circulars Issued ainto system under:
in the Last Twelve Months.
m ANO 7 907/ 7O/d 8' 77 r..,
No. of pages:
(M
'r' J'U Af L-mi_<2 -aw wa.--a ;:.~ a