ML19242A163

From kanterella
Jump to navigation Jump to search
Forwards IE Circular 79-13, Replacement of Diesel Fire Pump Starting Contactors. No Action Required
ML19242A163
Person / Time
Site: La Crosse File:Dairyland Power Cooperative icon.png
Issue date: 07/13/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Linder F
DAIRYLAND POWER COOPERATIVE
References
NUDOCS 7907310408
Download: ML19242A163 (1)


Text

p* *

  • Coq'o'

,e UNITED STATES 3

4

$\\

NUCLEAR REGULATORY COMMISSION

$ cIhe, c. g!)(. E REGION lli PDR Q.if[f 799 ROOSEVELT ROAD o,

GLEN E LLYN, ILLINOIS 60137

% '.Av

- JUL 131979 Docket No. 50-409 Dairyland Power Cooperative ATTN:

Mr. F. W. Linder General Manager 2615 East Avenue - South La Crosse, WI 54601 Gentlemen:

The enclosed IE Circular No. 79-13, is forwarded to you for infor-mation. No written response is required.

Should you have any questione related to your understanding of this matter, please contact this office.

Sincerely, f/

James G. Kepple Director

Enclosure:

IE Circular No. 79-13 cc w/ encl:

Mr. R. E. Shimshak, Plant Superintendent Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PER NSIC TIC Anthony Roisman, Esq.,

Attorney 790731ogag

U.S. NUCLEAR REGULATORY COMMISSICN OFFICE OF INSPECTION AND ENFORCEMENT REGION III July 13, 1979 IE Circular No. 79-13 REPLACEMENT OF DIESEL FIRE PUMP STARTING CONTACTORS Description of Circumstances:

On May 28, 1978, the Diesel Fire Pu=p failed to start remotely at Davis-Besse.

Unit 1 facility operated by Toledo Edison Company. The cause for failure was defective starting contactors. A subsequent investigation into the cause of a similar failure on January 18, 1978, at Commonwealth Edison Company's Dresden 2/3 Diesel Fire Pu=p identified a generic problem with Cu= mins Indus-t:ial Fire Pump Engines.

Discussion:

The investigation revealed that Cu=nins Engine Corgany issued a Service / Parts Topics No. 74T 13-3A announcing new components available for Industrial Fire Purps (NH-220-1F, N-855-F, N-855-F1, NT-855-F2 series engines) to improve operation of inline 6 cylinder Industrial Fire Pu=p Engines.

In this topic, C - ins recom= ends that when replacing the 118848 magnetic switch and 199573 DC relay contactor, use the new 217588 uagnetic switch. The new design com-ment has a 6 ampere draw whereas the old combination has approximately 3 atseres draw. Davis Besse and Dresden sites have i=plemented the corrective action recommended by C 4ns.

Reco= mended Actions for Licensees' Cons!deration:

All holders of operating licenses or construction permits should be aware of the potential problem of the type discussed above.

Because of the generic implications in this matter, it is recommended that both licensees of operating facilities and holders of construction permits conduct a review to determine if the above diesel fire pu=p engines are in use or planned for use at your facility (ies). If these engines are in use or planned for use, determine if the Cumina type 118848 Magnetic Switch and 199573 DC relay contactors are also e= ployed. For those engines which have these components,' develop a pro-gram for their replacement with the new 217588 Magnetic Switch.

No written response to this Circular is required.

If you require additional information regarding these matters, contact the Director of the appropriate NEC Regional Office.

{ DUPLICATE DOCUMENT

Enclosures:

{

l.

Cir ins Service / Parts Topics iEntire document previously entered No.

74 T 13-13A.

into system under:

2.

List of IE Circulars Issued

~7907/ 90/J s in the Last Twelve Months.

ANO r.$

No. of pages:

[f) 15

,io j

.w

. nn. m.

. ma m n a ww.. -,,

.