p aatc,

o 8['",y o,

UNITED STATES NR NUCLEAR REGULATORY COMMISSION

.g : " q ( j c

REGION lil

[

799 ROOSEVELT ROAD o,

/

be CLEN ELLYN ILLINOls 60137 a....

- Jtn.131979 Docket No. 50-329 Docket No. 50-330 Co2sumers Power Company ATTN:

Mr. Stephen H. Howell Vice President 1945 West Parnall Road Jackson, MI 49201 Gentlemen:

The enclosed IE Circular No. 79-13, is forwarded to you for infor-mation. No written response is required.

Should you have any questions related to your understanding of this matter, please contact this office.

Sincerely,

  • TI W

JamesG.Keppler[

Director

Enclosure:

IE Circular No. 79-13 cc w/ encl:

Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Ronald Callen, Michigan Public Service Commission Dr. Wayne E. North Myron M. Cherry, Chicago 4

'}t

^

7907310907

U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT REGION III Ju]y 13, 1979 IE Circular No. 79-13 REPLACEMENT OF DIESEL FIRE PUMP STARTING CONTACTORS Description of Circumstances:

On May 28, 1978, the Diesel Fire Pump failed to start remotely at Davis-Besse, Unit 1 facility operated by Toledo Edison Company. The cause for failure was defective starting contactors. A subsequent investigation into the cause of a similar failure on January 18, 1978, at Commonwealth Edisen Company's Dresden 2/3 Diesel Fire Pump identified a generic problem with Cummins Indus-trial Fire Pump Engines.

Discussion:

The investigation revealed that C

  • ns Engine Company issued a Service / Parts Topics No. 74T 13-3A announcing new components available for Industrial Fire Pumps (NH-220-1F, N-855-F, N-855-F1, NT-855-F; series engines) to improve operation of inline 6 cylinder Industrial Fire Pump Engines.

In this topic, Cu= mins recommends that when replacing the 115348 magnetic switch and 199573 DC relay contactor, use the nev 217588 magnetic switch. The new design component has a 6 ampere drav whereas the old combination has approximately 3 a= peres draw. Davis Besse and Dresden site, have i=plemented the corrective action recom= ended by Cummins.

Recommended Actions for Licensees' Consideration:

All holders of operating licenses or construction permits should be aware of the potential problem of the type discussed abcve.

Because of the generic implications in this matter, it is recommended tnat both licensees of operating facilities and holders of construction permits conduct a review to deteimine if the above diesel fire pu=p engines crc in use or planned for use at your facility (ies).

If these engines are in use or planned fer use, determine if the Cm mins type 118848 Magnetic Switch and 199573 DC relay contactors are also employed. For those em ines which have these components,'davelop a pro-gram for their replacement with the nev 2175E8 Magnetic Switch.

No written response to this Circular is required.

If you require additional information regarding these matters, contact the Director of the appropriate HRC Regional Office.

m.

IDUPLICATE DOCUMENT

Enclosures:

j 1.

Cmmins Service / Parts Topics 1 Entire document previously entered No.

74 T 13-13A.

linto FyStem under:

2.

List of IE Circulars Issued 4

in the Last Twelve Months.

')hO7/90/Ob' ANO G,.

/o No. of pages:

i n

$ F,

,) $ /

m p-

~

u

..m.-

~ ~ _.

.