R Rf Ggg
[
'o UNITED STATES
$ ),,.. g ',j NUCLEAR REGULATORY COMMISSION pgg
' * /
r REGION til h [j 799 ROOSEVELT ROAD o,
'N, GLEN ELLYN ILLINOls 60137
- JUL 131979 Docket No. 50-155 Docket No. 50-255 Consumers Power Company ATTN:
Mr. R. B. DeWitt Manager of Nuclear Plant Operations 212 West Michigan Avenue Jackson, MI 49201 Gentlemen:
The enclosed IE Circular No. 79-13, is forwarded to you for infor-mation. No written response is required.
Should you have any questions related to your understanding of this matter, please contact this office.
Sincerely,
- f../
WrS-JamesG.Kepplerp Director 7
Enclosure:
IE Circular No. 79-13 cc w/ encl:
Mr. C. J. Hartman, Plant Superintendent Mr. J. G. Lewis, Plant Superintendent Central Files Director, NRR/DPM Eirector, NRR/ DOR PDR Local PDR NSIC TIC Ronald Callen, Michigan Public Service Commission Anthony Roisman, Esq., Attorney Myron M. Cherry, Chicago
/j j,
- c. })
7007310VD(,'
U.S. NUCLEAR REGULATORY CO.TfISSION OFFICE OF INSPECTION AND ENFORCEMENT REGION III July 13, 1979 IE Circular No. 79-13
~
REPLACEME"I 0F DIESEL FIRE PUMP STARTING CONTACTORS Description of Circumstances:
On May 28, 1978, the Diesel Fire Pump failed to start remotely at Davis-Besse, Unit I facility operated by Toledo Edison Company.
The cause for failure was defective starting contactors. A subsequent investigation into the cause of a similar failure on January 18, 1978, at Commonwealth Edison Coepany's Dresden 2/3 Diesel Fire Pump identified a generic problem with Cu= ins Indus-trial Fire Pu=p Engines.
Discussion:
The investigatior. revealed that Cummins Engine Company issued a Service / Parts Topics No. 74T 13-3A announcing new components available for Industrial Fire Pumps (NH-220-1F, N-855-F, N-855-F1, hT-855-F2 series engines) to improve operation of inline 6 cylinder Industrial Fire Pu=p Engines.
In this topic, Cu= mins recommends that when replacing the 118848 magnetic switch and 199573 DC relay contactor, use the new 217588 magnet 1c switch. The new design component has r 6 ampere draw whereas the old combination has approximately 3 amperes draw. Davis Besse and Dresden sites have implemented the corrective at. tion recommended by Cu= ins.
Recommended Actions for Licensees' Consideration:
All holders of operating licenses or construction permits should be aware of the potential problem of the type discussed above.
Because of the generic implications in this matter, it is recommended that both licensees of operating facilities and holders of construction pertrits conduct a review to determine if the above diesel fire pu=p engines are in use or planned for use at your f acility(ie s).
If these engines are in use or planned for use, determine if the Cu= ins type 118848 Magnetic Switch and 199573 DC relay contactors are also employed. For those engines which hsve these components, develop a pro-gram for their replacement with the new 217588 Magnetic Switch.
No written response to this Circular is required.
If you require additional information regarding thete matters, contact the Director of the appropriate REC Regional Office.
-~
_ ~,.
_ 4
Enclosures:
1.
Cummins Service / Parts Topics Entire document previously entered e
No.
74 T 13-13A.
I into system under:
2.
List of IE Circulars Issued l 9O 7/9O/ Z @
in the I.ast Twelve Months.
h ANO No. of pages:
[p fg,
,g
.e
..u a
s p
,a.
s
~
.m