ML19241B010

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 781212-15
ML19241B010
Person / Time
Site: Crane  
Issue date: 01/15/1979
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML19241A994 List:
References
50-289-78-25, 50-320-78-38, NUDOCS 7907110538
Download: ML19241B010 (2)


Text

.

APPENDIX A NOTICE OF VIOLATION Metropolitan Edison Company Docket No. 50-320 Based on the results of the NRC inspection conducted on December 12-15, 1978, it appears that three of your activities were not conducted in full compliance with conditions of your NRC Facility License No. DPR-73 as indicated below:

A.

Appendix A to the License, in paragraph 6.8.1, states:

"Wri tten procedures shall be established, implemented and maintained..."

Licensee Procedure AP-1034, in paragraph 6.3, states:

"Should it become necessary to exceed the limits (of transient combustible material) for brief periods, the cognizant department head... must qualitatively evaluate any additional portable or temporary fire protection measures which must be taken in the area... while the limit... is exceeded, the area must be manned, or a fire watch patrol... at least once per hour be established."

Contrary to the above, empty cardboard boxes were stored in the cable spreading room, recording paper was stacked on temporary tables there, and a hot soldering iron was slugged into an outlet near the recording paper; however, the area was not manned nor had a fire watch patrol been e;tablished.

This item is an Infraction.

B.

Appendix A to the License, in paragraph 4.7.10.1.2(a)2, states :

"Each fire pump diesel engine shall be demonstrated operable at least once per 31 days:...The diesel stcrts from ambient conditions and operates for at least 20 minutes."

License Procedure AP-1010, in paragraph 6.6.1, states:

"A retest is required when initial test results fail to meet the acceptance criteria or when the test could not be entirely performei.

Retest results will be... evaluated, along with the original data sheets, by the Test Coordinator..."

07Nk f3R p

' Appendix.A jay 3 7 g-2 Con'rary to the above, a retest of steps 3.a, b and c of Surveil-lance Report 3303-M1, dated September 18, 1978, was not performed when the initial test failed, and the test coordinator did not sign the front page of the surveillance report to indicate that he had evaluated the test results.

This item is a Deficiency.

C. to the License, in paragraph G.9, states:

"By luly 31, 1978:

Provide additional fixed sealed-beam emergency lights to facilitate emergency operation at remote shutdown panels and facili ties... ".

Contrary to the above, additional emergency lights had not been installed in the cable-spreading room to facilitiate emergency operation of the remote shutdown panel.

This item is an Infraction.

}\\1