Requests Addl Info Necessary for Continuing Review of 770801 Submittal Re Degraded Grid Voltage.Proposed Tech Specs Should Include Trip Point on Second Level Voltage Protection & Description of How Voltage Monitors Comply W/Ieee 279
ML19225D036
Person / Time
Site: Millstone 
Issue date: 06/21/1979
From: Ziemann D
Office of Nuclear Reactor Regulation
To: Counsil W
NORTHEAST NUCLEAR ENERGY CO.
References
TASK-08-01.A, TASK-RR NUDOCS 7908030617
Download: ML19225D036 (2)


Text

] SIh

' [jf 4

UNITED STATES

^^

NUCLEAR REGULATORY COMMISSION j

WASHINGTON, D. C. 20555 S

I

%, * * * * * /

June 21, 1979 r

Docket No. 50-245 Mr. W. G. Counsil, Vice President Nuclear Engineering and Operations Northeast Nuclear Energy Company Post Office Box 270 Hartford, Connecticut 06101

Dear Mr. Counsil:

We are continuing our review of your August 1, '977 submittal concerning degraded grid voltage.

The submittal included preliminary technical specifications for emergency power system. We have concluded that the following are required to continue our review.

1.

Your pr~oposed technical specifications should include a trip point on the second level voltage protection on the 4160V bus including a casis for the trip point voltage and the time delay.

2.

Describe how the voltage monitors satisfy the requirements of IEEE Std. 279-1971.

Include sufficient information to enable us to verify compliance with the requirements.

To maintain our review schedule your response is requested within 30 days of

~

the date of this letter.

incerely, M

Dennis L. Ziemann, Q ief Operating Reactors 1 ranch #2 Division of Operating Reactors cc: See next page c(; )

o 7908030617 440 124 9

e

1 I

l Mr. W. G. Counsil June 21,1979 i

CC William H. Cuddy, Esquire l

Day, Berry A Howard Counselc s at Law One Constitution Plaza Hartford,. Connecticut 06103 Anthony Z. Roisman Natural Resources Defense Council 917 15th Street, N. W.

Washington, D. C.

20005 Northeast Nuclear Energy Company ATTN:

Superintendent Millstone Plant P. O. Box 128 Waterford, Connecticut C6365 l

Mr. James R. Himmelwright Northeast Utilities Service Ccmpany i

P. O. Box 270 i

Hartford, Connecticut 06101 l

Nuclear Regulatory Commission, Regior. I Of fice of Inspection and Enforcement i

ATTN: John T. Shediosky 631 Park Avenue 19406 King of Prussia, Pennsylvar#

i Waterford Public Library Rope Ferry Road, Route 156 Waterford, Connecticut 06385 l

i i

i l\\

b 1

440 125

.