{kk pa nec UNITED STATES f, _ '. e c g

'i '

n NUCLEAR REGULATORY COMMISSION

?

f

$.[

e'

/.

WASHINGTON, D. C. 20555 3 +c.

a A'

9,,,#

June 5, 1979 Docket No. 50-409 Mr. Frank Linder General Manager Dairyland Power Cooperative 2515 East Avenue south La Crosse, Wisconsin 54601

Dear Mr. Linder:

RE:

TCPIC VIII-3.A STATION S ATTERY TEST REQ'JIRE"ENT Enclosed is a copy of our revised safety assessment of Topic VIII-3. A, Station Battery Test Requirement.

This revision includes consideration of the comments received on the assessment issued by our letter dated fiarch 15, 1979.

Your letter dated April 17, 1979, proviced comments on the assessment.

This revision completes our assessment of Topic VIII-3. A which will be used as input to the integrated review of the La Crcsse Boiling Water Reactor.

If there are any errors in the facts of this revised assessment, please supply corrected information within 30 days of the date you receive this letter.

If no response is received within that time, we will assume that you have no further comments or corrections.

Sincerely,

%N Gknm Dennis L. Ziemann, uhief Operating Reactors Branch 72 Division of Cperating Reactors

Enclosure:

Revised Assessment for Topic VIII-3.A cc w/ enclosure:

See next page 3

2007190];$

mu

e Mr. Frank Linder June 5,1979 cc w/ enclosure:

Fritz Schubert, Esquire Staff Attorney Dairyland Power Cooperative 2615 East Avenue South La Crosse, Wisconsin 54601

0. S. Heistand, Jr., Esquire Morgan, Lewis & Bockius 1800 M Street, N. W.

Washington, D. C.

20036 Mr. R. E. Shimshak La Crosse Boiling Water Reactor Dairyland Power Cooperative P. O. Box 135 Genoa, Wisconsin 54632 Coulee Region Energy Coalition ATTN:

George R. Nygaard P. O. Box 1583 La Crosse, Wisconsin 54601 La Crosse Public Library 800 Main Street La Crosse, Wisconsin 54601 K M C, Inc.

ATTN:

Richard E. Schaffstall 1747 Pennsylvania Avenue, N. W.

Suite 1050 Washington, D. C.

200C6 h0/

0o6

SYSTE"ATIC EVALUATICH PROGF#1 BATTERY CAPACITY TESTS LACROSSE DOCKET NO: 50-409 Tepic VII!-3.A Station Battery Test Recuirements The objective of this review is to assure that the onsite Class IE battery capacity to supply all safety related I C Icads is verified by periodic testing.

The testing should be in accordance with IEEE Standard 450-1975, IEEE Standard 303-1974 ETP EICSS 6 ard the " Standard Technical Specifications for General Electric Soiling Water Reacters" (NUREG-0123).

The required tests are as follows:

1.

At least once per 18 months, during shutdown, a tattery service test should be performed to verify that the batte y capacity is acequate to supply and maintain in operable status all of the actual emergency loads for 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.

2.

At least once per 60 mcnths, during shutdown, a cattery discharge test should be performed to verify that the battery capacity is at least ca; of the manufacturer's rating.

The technical specifications for the LaCross> Nuclear Station include in Section 5.2.11.2.3.2 the above periodic batt.cy service and discharge tests.

Further, the battery service test is performed to verify that the battery caoacity is acequate to suoply and maintain in aceraole status all cf the actual emergency loads for 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />, rather than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> as required by the current staff criteria discEssed above. Therefore, the Lacrosse Nuclear

' tation complies with current licensing requirements for station battery cloacity tests. No additional SEP action is necessary.

409 0o7 June 5, 1979

References 1.

" Lacrosse Technical Specifications," Caf ryland Power Cooperattve, 2.

Standard Review Plan, Appendix 7-A, BTP EICSB 6, "Ca:acity Test Recuirements of Station Batteries - Te:hnical Specifications,"

U.S. Nuclear Regulatory Co=ission, 3

"IEEE Stancard Criteria for Class IE Peer Systems for Nuclear Poner Generatin; Stations," Std. No. 305-1974, The Institute of Electrical and Electronics Engineers, Inc.

4 "IEEE Recomended Practice for Maintenance, Testing and Replace.ent of Large Lead Storage Batteries for Std. No. 450-1975, The Institute of Ele:trical 'and Electronics Engineers, Inc, 5

" Standard Technical Spe:f ficatiens for General Electric Sailing 'n'ater Reactors," NUREG-Cl23, U.S. Nuclear Regulatory Comissicr.,

6.

Transmittal dated A:ril 17, 1979, frca Frank Linder, Dairyland Pcwer Cccperative to Direc:cr cf tiucle; Oeac::r Regulation.

i

)