ML19224D648

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-14, Seismic Analysis for As-Built Safety-Related Piping Sys. Action Required
ML19224D648
Person / Time
Site: Zimmer
Issue date: 07/02/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Borgmann E
CINCINNATI GAS & ELECTRIC CO.
References
NUDOCS 7907130258
Download: ML19224D648 (1)


Text

\\hk/

+jp ** " 8 %q'o, t

UNITED STATES E

, 7 7/(' 7, NUCLEAR REGULATORY COMMISSION

$ / ' '"#

REGION 111 0,, f$

[

799 ROOSEVELT ROAD

\\

.\\ s GLEN E LL*.'N, lLLINolS 60137 o

JUL 2 1979 Docket No. 50-358 Cincinnati Gas and Electric Company ATTN:

Mr. Earl A. Borgmann Vice President Engineering Services and Electric Production 139 East 4th Street Cincinnati, OH 45201 Gentlemen:

The enclosed IE Bulletin No. 79-14 is forwarded to you for action.

Written responses are required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, QA N^-f "

vJamesG.KeppIer Director Enclosure-IE Bulletin No. 79-14 cc w/ enc 1:

Mr. J. R. Schott, Plant Harold W. Kohn, Power Superintendent Siting Commission Central Files Citizens Against a Radioactive Director, NRR/DPM Environment Director, NRR/ DOR Helen W. Evans, State of PDR Ohio Local PDR NSIC VTIC 444 270

/

7907130dbb'

U.S. NUCLEAR REGULATORY COMMISSION f

0FFICE OF INSPECTION AND ENFORCEMENT REGION III July 2, 1979 IE Bulletin No. 79-14 SEISMIC ANALYSES FOR AS-BUILT SAFETY-RELATED PIPING SYSTEMS Description of Circumstances:

Recenty two issues were identified which can cause seismic analysis of safety-related piping systems to yield nonconservative results. One issue involved algebraic summation of loads in some seismic analyses. This was addressed in show cause ot O rs for Beaver Valley, Fitzpatrick, Maine Yankee and Surry.

It was also addretaed in IE Bulletin 79-07 which was sent to all power reactor licensees.

The other issue involves the accuracy of the information input for seismic analyses.

In this regard, several potentially unconservative factors were discovered and subsequently addressed in IE Bulletin 7'-02 (pipe supports) and 79-04 (valve weights). During resolution of these concerns, inspection by IE and by licensees of the as-built configuration of several piping systems revealed a number of nonconformances to design documents which could potentially affect the validity of seismic analyses. Nonconformances are identified in Appendix A to this bulletin.

Because apparently significant non-conformances to design documents have occurred in a number of plants, this issue is generic.

The staff has determined, where design specifications and drawings are used to obtain input information for seismic analysis of safety-related piping systems, that it is essential for these documents to reflect as-built cen-figurations. Where subsequent use, damage or modifications affect the con-dition or configuration of safety-related piping systems as described in documents from which seismic analysis input information was obtained, the licensee must consider the need to re-evaluate the amismic analyses to con-sider the as-built configuration.

y

~

n DUP _LICATE DUCUMENT 4g

[)

Entire document previously entered into system under:

l ANO b

b No. of geses:

9

._,,;