June 21, 1979 Docket Nos.
50-313 50-368 Arkansas Power and Light Company ATTN:
Mr. William Cavanaugh III Vice President of Generation and Construction P. O. Box 551 Little Rock, Arkansas 72203 Gentlecen:
Enclosed is IE Bulletin No. 79-02, Revision No. 1, which requires action by you with regard to your power reactor facilities with an operating license or a construction permit.
Should you have any questions regarding this Bulletin or the actions required by you, please contact this office.
Sincerely, 1
i darl V. Seyfrb Director
Enclosures:
1.
IE Eulletin No. 79-02 Revision No. 1 2.
List of IE Eulletins Issued in Last Twelve Months cc:
James P. O'Hanlon, Plant Manager Arkansas Nuclear One P. O.
Box 603 Russellville, Arkansas 72801
+-
L. Alexander, QC Supervisor I
f\\
. t 79071203 70-
UNITED STATES NUCLErl REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 IE Eulletin No. 79-02
.(Revision No. 1)
Date:
June 21, 1979 Page 1 of 6 PIPE SUPPORT BASE PLATE DESIGNS USING CONCRETE EXPANSION ANCHOR BOLTS Description of Circumstances-Since the issuance of IE Bulletin 79-02 on March 8, 1979, IE inspection experience and many inquiries from licensees indicate that additional informa-tion and clarification is needed. This revisivn is intended to serve that purpose. None of the requirements of the original Bulletin have been deleted, and the due date for completion of the reouested actions (July 6,1979' has not been changed.
The following text supersedes the text of Bulletin 79-02.
Changcs from the original text are identified by lines in the margin.
The pugose of this revision is to identify acceptable ways of satisfying the Bulletin requirements.
While performing inservice inspections during a March-April 1978 refueling outage at Millstone Unit 1, structural failures of piping supports for safety equipment were observed by the licensee.
Subsequent licensee inspections of undamaged supports showed a large percentage of the conci + anchor bolts were not tightened properly.
Deficiency reports, in accordance with 10 CFR 50.55(e), filed by Long Island Lighting Company on Shoreham Unit 1, indicate that design of base plates using rigid plate assumptions has resulted in underestimation of loads on some anchor bolts.
Initial investigation indicated that nearly fifty percent of the base plates could not be assumed to behave as rigid plates.
In addition, licensee inspection of anchor bolt installations at Shoreham has shown over fifty percent of the bolt installations to be deficient.
Vendor Inspaction Audits by NRC at Architect Engineering firms have shown a wide range of design practices and installation procedures which have been employed for the use of concrete expansion anchors.
The current trends in the industry are toward more rigorous controls and verification of the instal-lation of the bolts.
The data available on dynamic testing of the concrete expansion anchors show fatigue failures can occur at loads substantially below the bolt static capa _ _
cities due to material imperfections op. notch.bmos-
- """ T also show low cycle dynamic failure. atJ
, R,
(;
due to joint slippage.