ML19224D452

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-02,Revision 1, Pipe Support Base Plate Designs Using Concrete Expansion Anchor Bolts. Action Required
ML19224D452
Person / Time
Site: Dresden, Byron, Braidwood, Quad Cities, Zion, LaSalle  
Issue date: 06/21/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Brian Lee
COMMONWEALTH EDISON CO.
References
NUDOCS 7907120198
Download: ML19224D452 (1)


Text

4,,1 8

3 UNITED STATES g-NUCLEAR REGULATO."Y COMMISSION j,

i g

REGIOfJ lll

, 'i N 4} / -

e g

799 ROOSEVELT ROAD f

e

%d C

GLEN ELLYN, ILLINOIS 60137

.'JN 211979 Docket Nos. 50-10, 50-237, 50-249, 50-254, 50-265, 50-295, 50-304, 50-373, 50-374, 50-454, 50-455, 50-456 and 50-457 Commonwealth Edison Company ATIN:

Mr. Byron Lee, Jr.

Vice President Post Office Box 767 Chicago, IL 60690 Gentlemen:

Enclosed is IE Bulletin No. 79-02 Revision No.

1, which rcquires action by you with regard to your power reactor facilities with an operating license or a construction permit.

Should you have any questions regarding this Bulletin or the actions required by you, please contact this office.

Sincerely,

?cc h

/

/cdamesG.Keppler i Director Enc?osure:

IE Bulletin No. 79-02 Revision No. I cc w/ enc 1:

Mr. B. B. Stephenson, Mr. R. Cosaro, Project Station Superintendent Superintendent Mr. N. Kalivianakis, Central Files Station Superintendent Director, NRR/DPM Mr. N. Wandke, Station Director, NRR/ DOR Superintendent PDR dr. L. J. Burke, Site Local PDR Project Superintendent NSIC Mr. T. E. Quaka, Quality TIC Assurance Supervisor Anthony Poisman, Esq.,

Mr. R. H. Holyoak, Station Attorney Superintendent Mr. Dean Hansell, Office Mr. Gunner Sorensen, Site of Assistant Attorney Project Superintendent General P ' ' '.

){n()

0 '

-,4 T 007120S /9g

U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT REGION III June 21, 1979 IE Bulletin No. 79-02 (Revision No. 1)

(7906200183)

PIPE SUPPORT BASE PLATE DESIGNS USING CONCRETE EXPANSION ANCHOR BOLTS Description of Circumstances:

Since the issuance of IE Bull-*in 79-02 on March 8, 1979, IE inspection experience and many inquiries.:om licensees indicate that additional informa-tion and clarification is needed. This revision is intended to serve that purpose. None of the requirements of the original Bulletin have been deleted, and the due date for completion of the requested actions (July 6, 1979) has not been changed. The following text supersedes the text of Bulletin 79-02.

Changes from the original text are identified by lines in the margin. The Purpose of this revision is to identify acceptable ways of satisfying the Bulletin requirements.

Whi:e performing inservice inspections during a March-April 1978 refueling outq e J Millstone Unit 1, structural failures of piping supports for safety equipment were obsarved by the licensee.

Subsequent licensee inspections of undamaged supports showed a large percentage of the concrete anchor bolts were not tightened properly.

Deficiency reports, in accordance with 10 CFR 50.55(e), filed by Long Island Lighting Company on Shoreham Unit 1, indicate that design of base plates using rigid plate assumptions has resulted in underestimation of loads on some anchor bo'.ts.

Initial investigation indicated that nearly fifty percent of the base plates could not be assumed to behave as rigid plates.

In addition, licensee inspection of anchor bolt installations at Shoreham has shown over fifty percent of the bolt installations to be deficient.

Vendor Inspection Audits by NRC at Architect Engineering firms have shown a wide range of design practices and installation procedures which have been employed for the use of concrete expansion anchors. The current trends in the industry are toward more rigorous controls and verification of the instal-lation of the bolts.

.n The data available on dynaaic testing cf t h. ~ ~

~

^

~~

f fatigue failures crn occur at loads substan DUPLICATE DOCUMENT cities due to material imperfections or noti

[

also show low cycle dynamic failures at loa, Entire document previously entered

[

due to joint slippage.

into system under:

p bh ANO

  • Lines indicate changes to previous editio; 6

'ifj No. of pages:

7