ML19224C655

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 79-15, Deficient Procedures. No Action Required
ML19224C655
Person / Time
Site: Fort Saint Vrain Xcel Energy icon.png
Issue date: 06/07/1979
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Millen C
PUBLIC SERVICE CO. OF COLORADO
References
NUDOCS 7907060022
Download: ML19224C655 (1)


Text

CENTRAL FILE; f" "' %,o, UNITED STATES PDR:HQ y.j NUCLEAR REGULATORY COMMISSION R

- p ".f, g

u t.

E REGION IV

p'/[ O[#8 G11 RYAN PLAZA DRIVE, SUITE 1000 MSIC ARLINGTON TEXAS 76012 S, '

,o June 7, 1979

~

Jacket No.

50-267 Public Service Company of Colorado ATTN:

Mr. C. K. Millen Senior Vice President P. O. Box 840 Denver, Colorado 80201 Gentlemen:

This Information Notice is provided as an early notification of a possibly significant matter. It is expected that recipients will review the in'ormation for possible applicability to their facilities. No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular, Bulletin. or NRR Generic Letter will be issued to recommend or request specific licensee actions.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

f

?

/ ) &.

aW' 3,

KarlV.Ieyf'k Director

Enclosures:

1.

IE Information Notice No. 79-15 2.

List of IE Information Notices Issued in 1979 cc:

L. W. Warembourg, Nuclear Production Manager Fort St. Vrain Nuclear Station P. O. Box 368 Platteville, Colorado 80651 L. Brey, Manager, Quality Assurance

'3 0 (

' ) 'e u

(_

(.

7 90706 0 0A 2

UNITED STATES NUCLEAR REGULATORY COT!ISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Information Notice No.'79-15 Date:

June 7, 1979 Page 1 of 3 DEFICIENT PROCEDURES Summary On June 2,1979, at Arkansas Nuclear One - Unit 1, while observing conditions in the control room, an NRC inspector discovered an operational deficiency that could have resulted in the emergency feedwater system remaining isolated during subsequent power operation.

Description of Circumstances On June 2 while Arkansas Nuclear One - Unit 1 was preparing for startup, an NRC inspector in the control room found that during a surveillance test of the main feedwater check valves, the controls of the emergency feedwater system were positioned so that the system could not automatically respond if needed. The NRC inspector found that the test procedure being used bf the licensed operators did not include, as it should have, instructions either to bypass the emergency feedwater system or to return it to normal. The plant operators, without approved procedures covering this aspect of the test, bypassed the controls that would have started the feedwater system automatically.

Lacking a procedural requirement to return the system to normal, there was no assurance that emergency feedwater would be provided automatically if needed.

Following the Three Mile Island accident, the NRC required that operators be trained to initiate promptly the emergency feedwater system manually if it does not come on automatically. Thus, while no immediate safety hazard existed at the Arkansas Unit I plant because of the improper action, the NRC staff is concerned about the potential safety hazard of leaving the emergency feed'.ater system in the bypassed condition, about the possibility that other procedures at the Arkansas plant may be deficient and about the fact that the operators deviated from procedures in performing the surveillance test.

Arkansas Po.2r and Light Company has returned the plant to cold shutdown.

The June 2, 1979, NRC Order confirmed the requirement for a cold shutdown until the Commission staff is satisfied with the utility's method of con-trolling the development of operating procedures, the adequacy of existing procedures, and until there is assurance that operators will not deviate from those procedures.

DUPLICATE DOCUMENT Entire document previously entered into system under:

7 9670 20/W ANO ne -

.,3 No. of pages:

7

?

"?'

-