._

t yfo fa arcy.

f o,

UNITED STATES fy $p e (

7- ~

',' i NUCLEAR REGULATORY COMMISSION C

R E GION'l 0,,

?

A

[

631 PA9K AVENUE k,

>' " [

KING OF PRUSSIA, PENNSYLVANI A 19406 May 29, 1979 Docket Nos. 50-322 50-516 50-517 Long Island Lighting Company ATTN:

Mr. Andrew W. Kofford Vice President 175 East Old Country Road Hicksville, New York 11801 Gentlemen:

This Information Notice is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities.

No specific action or response is requested at this time.

If further NRC evaluar. ions so indicate, an IE Cir-cular or Bulletin will be issued to recommend or request scecific licensee actions.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

Sincerely,

/

/ fM fo h-- -

/

b '42. Boyce H. Grier Director

Enclosures:

1.

IE Information Notice No. 79-13 w/ enclosures 2.

List of Information Notices Issued in 1979 cc w/encls:

J. P. Novarro, Project 'lanager Edward M. Barrett, Esq., General Counsei Edward J. Walsh, Esq, General Attorney T. F. Gerecke, Manager, Engineering QA Department 57 7907030037,

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

205b5 IE Information Notice No. 79-13 Date:

May 29, 1979 Page 1 of 4 INDICATION OF LOW WATER LEVEL IN THE OYSTER CREEK REACTOR Summary A loss of feedwater transient at the Oyster Creek facility on May 2, 1979, resulted -in a significant reduction in water inventory within the reactor core shroud area as measured by one set of water level instruments (triple low level),

while the remaining level instruments, sensing from the reactor annulus area indicated water levels above any protective feature setpoint (Figure 1). The water level within the core shroud area was reduced below the " trip'e low level" setpoint of 4-feet, 8-inches above the top of the fuel.

Subsequent analysis by the licensee has determined that the minimum collapsed water level (solid, without steam voids) over the top of the fuel was 1 to 1-1/2 feet.

Coolant sample analyses and offgas release rates indicate that no fuel damage occurred.

General Oyster Creek is a non-jet pump BWR with licensed power of 1930 MWt.

The plant was first made critical May 3, 1969.

Status Before Transient Operating at near full power with the main parameters at levels as follows:

1895 MWt power level 79" Yarway (13'4" over top of fuel) reactor water level 1020 psig reactor pressure 7.1x106 #/hr feed flow 4

14.8x10 gpm recirculation flow rate (4 pumps) 12 psid core ap Equipment Out of Service (005)

"D" recirc pump OOS due to seal cuult

~'

"B" startup transformer 00S for inspe DUPLICATE DOCUMENT

Entire document previously entered into system under:

190(p06 O/6f ANO 1

No. of pages:

[f 1