2 4 AUG 1Fd APPENDIX A NOTICE OF VIOLATION Metropolitan Edison Company Docket No. 50-320 Based on the results of the NRC inspection conducted on July 18-21 and July 31 - August 3,1978, it appears that one of your activities was not conducted in full compliance with conditions of your Facility License No. OPR-73 as indicated below.

This item is an Infraction.

10 CFR 50, Appendix B, Criterion V, states, in part:

" Activities affecting quality shall be prescribed by... procedures...and shall be accomplished in accordance with these... procedures...."

The accepted Operational Quality Assurance Program (FSAR Section 17.1.5.1) states, in part:

"The Met-Ed Quality Assurance Plan...contains the J

.equirements that activities affecting quality be documented by

/!

/

instruction, procedures...."

}

Mechanical Construction Procedure, MCP-2-2, Revision 12, specifies l

the requirement that weld rods, if not issued, shall be placed in j

holding / storage ovens and maintained at 250 F + 25'F.

Contrary to the above, on July 20, 1978, the holding / storage furnace containing the low hydrogen weld rods was found to be at an indicated temperature of 190 F.