ML19210D433
| ML19210D433 | |
| Person / Time | |
|---|---|
| Site: | Hartsville |
| Issue date: | 09/28/1979 |
| From: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| To: | |
| Shared Package | |
| ML19210D417 | List: |
| References | |
| 50-518-79-22, 50-519-79-22, 50-520-79-22, 50-521-79-22, NUDOCS 7911270062 | |
| Download: ML19210D433 (1) | |
Text
.
APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority License Nos. CPPR-150 Hartsville Nuclear Plant CPPR-151, CPPR-152
& CPPR-153 Based on the NRC inspection September 5-7, 1979, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below. These items have been categorized as described in correspondence to you dated December 31, 1974.
As required by Criterion V of Appendix B to 10 CFR 50, and implemented by PSAR Section 17.1A.5, " Activities affecting quality shall be prescribed by documented instructions, procedures,...and shall be accomplished in accord-ance with those instructions, procedures,...". TVA Specifications N6C-875 and G-9 require that three point compaction tests be made by the site soils laboratory on the spray pond central and support fill at least once for each 50 routine test on each soil type placed to confirm correlation with the central laboratory compaction curves.
Contrary to the above, more than 50 routine tests have been performed on CL soils since July of 1978 and no three point compaction tests have been made to date.
This is an infraction.
e
/'
7911270 06A
,