Second Interim Deficiency Rept:On 790507,general R&D Program Tests Revealed Cracking of heat-affected Zone of Welded Stud Anchors.Final Rept by 791221
ML19210D091
Person / Time
Site: Hartsville  Tennessee Valley Authority icon.png
Issue date: 08/13/1979
From:
TENNESSEE VALLEY AUTHORITY
To:
Shared Package
ML19210D076 List:
References
NCR-CEB-79-16, NUDOCS 7911200517
Download: ML19210D091 (1)


Text

..,..

e o

HARTSVILLE NUCLEAR PLANTS A AND B NCR CEB-79-16 REPORT NO. 2 (INTERIM)

TENSILE ANCHOR CAPACITIES LOWER THAN ASSUMED IN DESIGN ALLOWABLES Description of Deficiency Progressive cracking of the heat affected zone of welded stud anchors in flexible plate connections has occurred in TVA general This results in lower tensile research and development program tests.

anchor capacities than assumed in establishing design allowables.

Interim Procress TVA has completed its testing program for welded stud anchors with flexible plate connections. The data is presently beingWe evaluated and corrective action will be taken as necessary.

anticipate transmitting the final report to the NRC on or before December 21, 1979.

13/3

J 53 9112 00.,y g

,